Data Sheet

Burner Equipment
Equipment Fuel Description
Control Cabinet Gas, Gas/#2 Oil
NEMA 1A with hinged door
Control Voltage Transformer Gas, Gas/#2 Oil
Included
Motor Starter Gas, Gas/#2 Oil
Magnetic starter with overload protection
Fusing Gas, Gas/#2 Oil
Control circuit only
Ignition Gas, Gas/#2 Oil
Gas/Electric pilot
Signal Lights Gas, Gas/#2 Oil
(4) - power on, fuel valve open, call for heat, flame failure
Air Flow Safety Switch Gas, Gas/#2 Oil
All Models
Gas Train Gas, Gas/#2 Oil
UL gas train for minimum inlet pressure indicated on Burner
Information table. Assembled, wired and mounted on unit
consisting of the following:
Manual shut off valve
Gas pressure Regulator
Manual leak test valve
40 & 50: 2 Gas Valves
150 & Larger: 2 Gas Valves
Main Gas Valve: Motorized type
Auxillary gas valve: Solenoid type
60 -125: Single Motorized Gas Valve with Proof of closure
60 & Larger: High and Low gas pressure switches
Oil Pump Gas/#2 Oil
Remote oil pump set with motor and accessories mounted on
boiler skid
Oil Firing Type Gas/#2 Oil
100 - 250: Pressure Atomizing
300 and larger: Air Atomizing
Pilot Gas Controls Gas, Gas/#2 Oil
All models have gas/electric pilot, manual pilot shut-off valve, pilot
gas pressure regulator and solenoid gas valve
Fuel Changeover Gas/#2 Oil
Manual switch
Flue Gas Recirculation Gas, Gas/#2 Oil
Induced flue gas recirculation, no external fan is required
SERIES LN3
LN-2 7/9/2013