Install Instructions
68
Boiler
Model
Burner
Input
(GPH)
Burner
Model
Nozzle
Head
Setting
Air
Setting
Pump
Pressure
(PSI)
Air Tube
Type
Insertion
Depth
(Inch)
Approx.
Shipped
CO
2
(%)
Baffle
Location
(pass)
Approx.
Stack Temp.
Increase
Without
Baffles °F
(2)
Approx.
Breech
Pressure
(" w.c.)
(3)
Baffles IN
Approx.
Overfire
Pressure
(" w.c.)
(3)
Baffles OUT
Approx.
Overfire
Pressure
(" w.c.)
(3)
MPO-IQ115 0.82 EZ-LF
0.65 x 45A
Delavan
0.75 60 150 12D 2-5/8 11.5 2
nd
& 3
rd
84 0 +0.040 +0.020
MPO-IQ147 1.05 EZ-66
0.85 x 45AS
Danfoss
2.0 40 150
Conical
Wrap
2-5/8 11.5 2
nd
65 0 +0.040 +0.020
MPO-IQ189 1.35 EZ-66
1.10 x 45B
Delavan
3.5 50 150
Conical
Wrap
2-5/8 11.5 2
nd
39 0 +0.040 +0.030
MPO-IQ231 1.65 EZ-66
1.35 x 45B
Hago
5.5 60 150
Conical
Wrap
2-5/8 11.5 2
nd
18 0 +0.050 +0.030
Notes
(2)
The increased stack temperature with the baffles removed is an approximation, based on a constant supply temperature of 180°F and 11.5% CO
2
. Actual field conditions may be different.
(3)
These values are minimum and could be as much as -.03" w.c., more without impacting performance. Pressures based on 11.5% CO
2
. Example: MPO-IQ231 could have a breech pressure of
-.03" w.c. and an overfire pressure of .020" w.c.
4) Single stage fuel pump is standard, two-stage fuel pump is optional. Burner manufacturer has preset single stage fuel pump to settings shown in table above. Two-stage fuel pump is factory
set at 140 PSI and must be readjusted to settings shown
above during burner start-up.
TABLE 8B: CARLIN BURNER SPECIFICATIONS
SECTION XII: REPAIR PARTS (continued)