10. Inspect burner swing door insulation for damage and
proper type.
By design, for all models, cast bars on front section
between the combustion chamber, and, between the
left and right side 2nd and 3rd pass ueways should
make an impression in door insulation to seal the
chambers.
By design, door insulation on model MST629
will
have two by-pass pockets cast into the insulation
centered on the bar between the combustion
chamber and 3rd pass ueways. By design, door
insulation on models MST288, MST396 & MST513
will not have any by-pass pockets. If insulation is
damaged, or, improper type regarding the pockets, it
must be replaced.