f. Not less than 1 ft from the nearest surface of the
terminal to a roof soffit.
g. Not directly above, or, not less than 5 ft horizontally
from an oil tank vent.
h. Not less than 2 ft from nearest surface of terminal
to an adjacent building.
B. INSTALLATION OF THE VENT HOOD TERMINAL
1. Inspect Direct Vent Conversion Kit Carton for
damage. DO NOT install if any damage is evident.
2. Direct Vent Conversion Kit Carton includes (see
Figures 18, 19 and 20):
Direct Vent Hood Assembly (consists of Vent
Hood Body and Vent Hood Tee) – 1 pc
Backing Plate – 1 pc
Vacuum Relief Valve VRV-4 – 1 pc
Hardware Bag (includes high temperature
sealant, fasteners and inner pipe clamps) – 1 pc
Appliance (Boiler Flue Outlet) Adapter – 1 pc
Appliance Clamp Halves – 2 pcs
Cover Sleeve Assemblies – 2 pcs
Cover Ring Assemblies – 2 pcs
3. Remove vent system components from carton and
set aside.
4. Separate the vent hood tee from the vent hood body
and set aside for later use.
5. After determining the location of the venting system
termination, cut the square hole in the wall sized
according to “L” dimension in Table 5, see Figure
17.
6. Wood or vinyl siding should be cut, so that vent
hood base plate mounts directly on the wallboard to
provide stable support. If siding thickness exceeds
½”, use a spacer bar or board behind the vent hood
mounting (base) plate. See Figure 18.
a. Seal the backside of the vent hood base plate
around the outer pipe of the vent hood with a bead
of high-temperature silicone sealant (provided
in Bagged Hardware).
b. Mount the vent hood body from outside, through
the wall, keeping the outer pipe centered in the
hole.
c. Fasten the vent hood body to the outside wall
with appropriate fasteners (installer provided).
d. Seal the edges of the vent hood base plate to
the wall with a high-temperature silicone sealant
(provided in Bagged Hardware).
e. While inside, position the backing plate over
the outer pipe and fasten to inside wall with
appropriate fasteners (installer provided).
Figure 17: Wall Cutout Dimensions
Boiler Model No.
Direct Vent
Conversion Kit
Part No.
"L" Dimension
(Inch)
MPO-IQ147B
MPO-IQ189B
102130-02
MPO-IQ231B 102130-03
Table 5: Wall Cutout Dimensions
Figure 18: Vent Hood Body Installation
5 Direct Venting / Air Intake Piping (continued)