Product Overview
16
103859-12 - 8/19
MPO-IQ
Installation & Service Manual
NPT tapping on tee. See Figure 5.
Step c.  Pipe discharge of relief valve as shown in 
Figures 10 and 11. Installation of the relief valve 
must be consistent with ANSI/ASME Boiler and 
Pressure Vessel Code, Section IV.
  WARNING
 Safety valve discharge piping must be piped near 
floor to eliminate potential of severe burns. Do not 
pipe in any area where freezing could occur. Do 
not install any shut-off valves, plugs or caps.
2.  Install drain valve, see Figure 6.
Step a.  Apply pipe sealant to both ends of 1-1/4" 
NPT x 5" lg. nipple. Thread nipple into 1-1/4" 
NPT lower rear tapping on rear section.
Step b.  Thread 1-1/4" x 1-1/4" x 3/4" NPT tee on 
opposite end of 5" lg. nipple installed in Step a.
  NOTE: Based on access for servicing and 
location of sewer or floor drain, when tightening 
these fittings, determine if drain valve is to be 
located on the left or right side.
  Tighten nipple and tee into 1-1/4" NPT lower rear 
tapping on rear section until joints are water tight 
for desired position.
Step c.  Apply sealant to 3/4" NPT thread on drain 
valve. Thread into 3/4" NPT tapping on side 
outlet of tee. Use hex nut portion to tighten valve 
until water tight.
3.  Connecting field wiring, refer to Figures 7, 28A thru 
28C.
Step a. Locate the black, white and green harness 
wires labeled "120V Power Supply" inside internal 
junction box, see Figure 7. Using wire nuts, 
connect the 120 volt power supply field wires 
to the harness wires. 
Step b. Locate the yellow and white wires labeled 
"System Circulator" inside internal junction box, 
see Figure 7. Using wire nuts, connect the 120 
volt field wires to the harness wires.
Step c.  If applicable, locate the violet and white wires 
labeled "DHW Circulator" inside internal junction 
box, see Figure 7. Using wire nuts, connect the 
120 volt field wires to the harness wires.
Step d. If applicable, locate the brown wire labeled 
"DHW Demand" inside internal junction box, see 
Figure 7. Using wire nut, connect the 120 volt 
field wire to the harness wire.
Step e.  24V thermostat field wiring will enter through 
5/16" snap bushing located on either the right 
side or left side jacket panel. Connect the 24V 
wiring from the thermostat to the "T-T" terminals 
on the Option Control Panel.
Step f. To connect other external devices, refer 
to the instructions included with these devices.
4.  Installing Boiler-ECOM harness (only used with 
Honeywell Oil Primary).
Figure 6: Piping Arrangement for Drain Valve and Indirect Water Heating Return
2 Packaged Boiler Assembly - Trim & Controls (continued)
!










