Product Overview
26
103859-12 - 8/19
MPO-IQ
Installation & Service Manual
B.  CHIMNEY CONNECTOR
1.  A chimney connector (vent pipe) is used to connect 
the boiler to the base of the chimney. The chimney 
connector should be kept as short as possible. The 
horizontal length of the chimney connector shall not 
be greater than 10 feet.
  NOTE: Secure chimney connector to cast iron 
smokebox collar with three (3) #10 x ½" self drilling 
hex head TEK screws provided in miscellaneous 
parts carton. Locate screws around perimeter of 
connector as shown in Figure 15 and approximately 
½" in from edge. Use drill with 5/16" hex bit to drive 
screws through connector and smokebox collar.
DANGER
   The chimney and connector shall be inspected 
annually for signs of debris and corrosion. Loose 
mortar at the base of the chimney may be a sign 
of condensate damage to the chimney. A chimney 
professional shall be contacted immediately to 
examine the damage and recommend a solution. 
Long term operation while in this condition may 
cause a venting failure and force flue gases into 
the living space. If the chimney is to be re-lined 
use the recommendations in NFPA 31, Appendix E 
or CSA B139.
2. Vent Connector shall be any of the following and 
of the same size as the outlet of boiler.
a.  Type L or a factory built chimney material that 
complies with the Type HT requirements of 
ANSI/UL 103. Install in accordance with listing 
and manufacturer’s instructions.
b.  Steel pipe having resistance to corrosion 
and heat with a minimum wall thickness of 24 
Gauge (0.024”).
DANGER
  Any signs of condensate seepage at the base of 
the chimney shall be inspected immediately. The 
discoloration may be a sign of chimney damage 
and must be remedied immediately.
C.  DRAFT
1.  The natural draft generated through a chimney is 
dependent on several factors including, chimney 
height, temperature of flue gases, cross section area 
of chimney, chimney wall insulation value, dilution 
air and total volume of flue gases, to name a few.  
Make sure that the boiler has been running for at 
least 5 minutes before measuring the draft.
2. Minimum Draft at Breech (Canopy) – The draft 
induced by a chimney must create at least a 
pressure of 0 (zero) inches water column (“ w.c.) 
at the pressure tapping on the canopy mounted on 
rear of boiler (see Figure 15). The pressure at the 
canopy cannot be positive since this could create a 
condition that allows flue gas by-products to escape 
from the draft regulator. A negative pressure reading 
up to -.03 inches water column is acceptable for 
proper operation. (See Tables 15A thru 15C and 
16) Burner Specifications at the rear of this manual 
for more details)
3.  Minimum Overfire Pressure – The overfire 
pressure is another piece of information that is 
often measured, however this should be done for 
observation purposes only! The breech pressure 
must be used to qualify the draft condition. See 
Tables 15A thru 15C and 16 for more details 
as a guide. Actual draft and temperature 
measurements may be different then those values 
in the table.
D.  STACK TEMPERATURE
1.  The temperature of the flue gases has a significant 
effect on the amount of draft created in a vertical 
chimney as well as the propensity to create 
condensate. The higher the stack temperature, the 
greater the amount of draft that can be generated.  
A lower stack temperature not only reduces the 
amount of draft that can be created but it also 
increases the possibility that the flue gases could 
condense in the chimney connector or stack.
2.  NFPA 31 and CSA B139 have information to help 
the installer make an appropriate choice of venting 
materials. In some cases a chimney may have to 
be lined to create sufficient draft. In other cases, 
the chimney may have to be lined to prevent 
the corrosion of a masonry chimney. Consult 
with a chimney specialist knowledgeable on the 
requirements for chimney requirements in your area.
Figure 15: Smokebox Pressure Tapping
for Checking Draft at Breech
4 Natural Draft Venting (continued)
!
!










