Installation and Operation Manual
63
a.  Temperature and Flow Requirements – An 
existing parallel piping system may be used, 
provided the return water is not below 80°F and 
the return water temperature is not more than 
80°F less than the boiler outlet temperature. A 
ow analysis should be performed to determine 
the ow through the boiler when the minimum 
(and smallest) and maximum number of zones 
are activated. 
  Sufcient ow through the boiler must be 
maintained. The recommended maximum 
temperature difference between the boiler supply 
and return water is 40°F. However, a maximum 
delta T of 80°F across the boiler is allowable. 
A minimum boiler supply water temperature of 
130°F must be maintained to avoid sustained 
condensing within the combustion chamber.
b.  Primary/Secondary Piping - If the conditions 
above cannot be met, then parallel piping 
systems must be converted to an arrangement 
that will provide the proper water ow through 
the boiler at the proper temperatures. Primary/
Secondary piping is a common method for 
isolating the boiler from the system. The 
concept must be for the boiler loop to inject 
heat into a primary loop, provided the return 
water into the boiler is at least 80°F. A by-pass 
containing two closely spaced tees must be 
installed to de-couple the boiler loop from the 
primary loop (see Figure 51). The converted 
system should resemble Figure 52. Care must 
be taken to avoid dead heading the system pump.  
Conversions should be reviewed and approved 
by a Consulting Engineer or other qualied 
professional to avoid system deciencies. 
Figure 51: Parallel Piping Conversion
c.  Alternate Piping Arrangements - Piping 
arrangements other than Parallel and Primary/
Secondary, such as System Bypass, are 
acceptable as long as they ensure that the ow 
and temperature requirements of the boiler are 
met.
d.  Glycol Antifreeze Solutions - Many systems 
today use ethylene or propylene glycol antifreeze 
solutions as a measure for freeze protection, as 
well as a pump lubricator and corrosion inhibitor.  
The properties of the glycol mixture have an 
impact on valve and pump sizing. All glycol 
solutions have a lower specic heat than water. 
This means that the glycol solution cannot 
transfer heat as well as pure water, resulting in 
the need for higher ow rates. In addition, the 
viscosity of the glycol solution is usually higher 
than water, requiring a higher pump head for the 
same given ow. Consult factory for specic 
applications, pump selection and ow rate.
e.  If this boiler is used in connection with refriger-
ation systems, the boiler must be installed so that 
the chilled medium is piped in parallel with the 
heating boiler using appropriate valves to prevent 
the chilled medium from entering the boiler. See 
Figure 53.
Figure 52: Typical Burnham Boiler -
Primary - Secondary Loop System
Figure 53: Recommended Piping for Combination 
Heating & Cooling (Refrigeration) Systems
  Multiple boilers are installed the same as single 
boiler installations. Each boiler loop will contain 
its own boiler circulator (see Figure 49b). 
The boiler circulator selection will maintain a 
constant and minimum ow through the boiler 
during every heat demand. The circulator 
must be properly selected, based on the design 
temperature between the boiler supply and boiler 
return. A boiler circulator must be used with a 
primary/secondary piping arrangement.










