Boiler Operating Requirements:
•  Minimum Return Water Temperature = 80°F
•  Maximum Delta T = 80°F
•  Minimum Supply Water Temperature = 130°F
Figure 50b: Alternate MPC Minimum Piping - Multiple Boiler Application
NOTES: For Boiler pipe sizes, ow rates, 
 pressure drops and other important  
 information and notes, refer to                        
 Figure 50a.