Installation and Operation Manual

60
Boiler Operating Requirements:
Minimum Return Water Temperature = 80°F
Maximum Delta T = 80°F
Minimum Supply Water Temperature = 130°F
Figure 49b: Recommended MPC Minimum Piping - Multiple Boiler Application
NOTES: For Boiler pipe sizes, ow rates,
pressure drops and other important
information and notes, refer to
Figure 49a.