Operating Instructions
18
105337-03 - 5/15
I. Operation F. Changing Adjustable Parameters (continued)
Control Repair Part Kit Part Number 106194-01
Altitude 0 - 2000 Ft.
Parameter K2-80-02 K2-100-02 K2-120-02 K2-150-02 K2-180-02
Maximum Heat Rate (RPM) 5100 5500 5100 5400 6000
Minimum Heat rate (RPM) 1600 1650 1600 2000 1800
Absolute Maximum Heat Rate (RPM) 5400 6900 5700 6300 6700
Minimum Light-off (RPM) 3500 3500 3500 3500 3500
Maximum Light-off rate (RPM) 4000 4000 4000 4000 4000
Altitude 2001 - 4500 Ft.
Parameter K2-80-24 K2-100-24 K2-120-24 K2-150-24 K2-180-24
Maximum Heat Rate (RPM) 6000 7450 6900 7200 7050
Minimum Heat rate (RPM) 1600 1850 1750 2000 1800
Absolute Maximum Heat Rate (RPM) 7565 7620 6984 7200 7150
Minimum Light-off (RPM) 3500 3500 3500 3500 3500
Maximum Light-off rate (RPM) 4000 4000 4000 4000 4000
Altitude 4501 - 7800 Ft.
Parameter K2-80-57 K2-100-57 K2-120-57 K2-150-57 K2-180-57
Maximum Heat Rate (RPM) 6200 7500 7050 7300 7200
Minimum Heat rate (RPM) 1800 2000 1800 2000 1900
Absolute Maximum Heat Rate (RPM) 7720 7680 7132 7300 7385
Minimum Light-off (RPM) 3500 3500 3500 3500 3500
Maximum Light-off rate (RPM) 4000 4000 4000 4000 4000
Altitude 7801 - 10100 Ft.
Parameter K2-80-80 K2-100-80 K2-120-80 K2-150-80 K2-180-80
Maximum Heat Rate (RPM) 7000 7900 7240 7450 7500
Minimum Heat rate (RPM) 1900 2000 1800 2000 1900
Absolute Maximum Heat Rate (RPM) 7950 7975 7360 7450 7760
Minimum Light-off (RPM) 3500 3500 3500 3500 3500
Maximum Light-off rate (RPM) 4000 4000 4000 4000 4000
Table 4: Parameters Changed Using the Boiler Type Parameter Selections: