Install Instructions

14
TABLE 7.1: SUMMARY OF HORIZONTAL VENTING OPTIONS
VENTOPTION# 1 2 3
CLASSIFICATIONUSEDINTHIS
MANUAL
HORIZONTAL
CONCENTRIC
HORIZONTAL
TWINPIPE
HORIZONTAL
CONCENTRIC
ILLUSTRATEDINFIGURE 7.2
7.3 7.2
VENTPIPEPENETRATION
THROUGHSTRUCTURE
WALL WALL WALL
AIRINTAKEPIPEPENETRATION
THROUGHSTRUCTURE
WALL WALL WALL
VENTPIPESIZE
60/100mm
CONCENTRIC
3”
80/125mm
CONCENTRIC
AIRINTAKEPIPESIZE
3”
MAXIMUMLENGTH
VENT
FCM070 32ft 55ft 55ft
FCM090 32ft 55ft 55ft
FCM120 18ft 55ft 55ft
INLET
FCM070 32ft 55ft 55ft
FCM090 32ft 55ft 55ft
FCM120 18ft 55ft 55ft
MINIMUMLENGTH
VENT
FCM070 10in 2ft 2ft
FCM090 10in 2ft 2ft
FCM120 10in 2ft 2ft
INLET
FCM070 10in 2ft 2ft
FCM090 10in 2ft 2ft
FCM120 10in 2ft 2ft
VENTTERMINAL
60/100mm
CONCENTRIC
P/N8110701
P/N101494-01
CONCENTRIC
orP/N101544-01
SNORKEL
AIRINTAKETERMINAL 3”90ELBOW
VENTMATERIAL
U.S.Boiler
60/100mmVENT
COMPONENTS
SHOWNIN
TABLE7.4a
(Note #1)
APPROVED
STAINLESS
STEELVENT
SYSTEMSHOWN
INTABLE7.5
U.S.Boiler
80/125mmVENT
COMPONENTS
SHOWNIN
TABLE7.4b
AIRINTAKEMATERIAL
GALVANIZEDOR
PVC
Note #1: In Vent Option #1, the 80/125mm concentric straight section (P/N 101162-01) shown in Table 7.4a may be used
between the boiler and the rst 80/125 x 60/100 reducing elbow. If this is done, the overall maximum vent length is still
restricted to that shown for Vent Option #1 in Table 7.1 above.
HorizontalTerminalClearanceRequirements(Continued):
• Ventterminalmustbeatleast6feetfromaninsidecorner.
• Undercertainconditions,waterintheuegasmaycondense,andpossiblyfreeze,onobjectsaroundtheventterminal
includingonthestructureitself.Iftheseobjectsaresubjecttodamagebyuegascondensate,theyshouldbemovedor
protected.
• Ifpossible,installtheventandairintaketerminalsonawallawayfromtheprevailingwind.Reliableoperationofthis
boilercannotbeguaranteediftheseterminalsaresubjectedtowindsinexcessof40mph.
• Airintaketerminalmustnotterminateinareasthatmightcontaincombustionaircontaminates,suchasnearswimming
pools.SeeSectionIVfor moreinformationonpossiblecontaminates.