Install Instructions
43
EMP
Installation & Service Manual
109529-03 - 11/19
Figure 33: R7284 Oil Primary Terminals,
Display and Function Buttons
 • Check contacts between ignitor and the 
   electrodes.
• Check the oil pump pressure.
• Check the piping to the oil tank.
• Check the oil nozzle, oil supply and oil filter.
b.  Check Safety Features
  Safe Start:
•  Place a jumper across cad cell terminals.
•  Follow procedure to turn on burner 
  Burner must not start, indicator light turns 
on and control remains in Idle Mode.
•  Remove jumper.
c.  Simulate Ignition or Flame Failure:
• Follow procedure to turn on burner.
• Check cad cell resistance. If resistance is 
    below 1600 OHMS and burner runs  
 beyond safety cut-out time, cad cell is 
 good.
  • If safety switch shuts down burner and 
  resistance is above 1600 OHMS, open 
  line switch to boiler. Access cad cell 
  under ignitor, clean face of cad cell  
  and see that cell is securely in socket, 
  see Figure 34. Check gasket around 
  perimeter of ignitor lid for proper seal. 
  If gasket is missing or damaged, replace 
  gasket. Room light can effect cad cell 
  resistance. Reset safety switch. 
 • Close line switch to boiler. If burner 
 starts and runs beyond safety switch cut- 
 off time, cell is good. If not, install new 
 cell.
• Close hand valve in oil supply line.
• Failure occurs, device enters Recycle 
Mode.
Figure 34: Cad Cell Location
K.  CHECK HIGH LIMIT
1.  Adjust system thermostat(s) to highest setting.
2.  Allow burner to run until boiler water 
temperature exceeds high limit setting. The 
burner should shut down and circulators 
continue running.
3.  Allow the temperature to drop below control 
setting. The burner must restart.
4.  Boiler installation is not considered complete 
until this check has been made.
L.  IF CONTROLS MEET REQUIREMENT outlined 
in Paragraphs I thru K.
1.  Allow boiler to operate for approximately 30 
minute, confirm the boiler and system have no 
leaks.
2.  Reset thermostat(s) at desired setting.
M.  IF CONTROLS  DO  NOT MEET 
REQUIREMENTS outlined in Paragraphs I 
thru K, replace control and repeat checkout 
procedures.
  WARNING
 Cad Cell Jumper must be removed after this 
check.
8 System Start-Up (continued)
!
 • Device tries to restart system after   
 approximately 60 seconds.
• After third Recycle Mode trial, safety 
switch locks out within safety switch 
timing indicated on label and control 
enters Restricted Mode. Ignition and 
motor stop and oil valves closes.
d.  Power Failure Check: After Flame is 
established, turn the power off to the 
control/burner. The burner should shut 
down safely. When power is restored a 
normal ignition sequence should be started.