G.   INSTALLING THE AIR INTAKE PIPING FROM  
DIRECT VENT TERMINATION TO BURNER  
OUTSIDE  AIR  ADAPTER
1.  Use 4" diameter galvanized single wall vent pipe 
and fittings, available at most heating distributors, 
to connect burner outside air adapter to Direct 
Vent Termination air intake collar. 
2.  Maximum air intake pipe length is 40 equivalent 
feet.
 Figure 21: Vent Pipe Assembly to Vent Termination 
Inner Pipe & Appliance Adapter
  WARNING
 DO NOT reduce size of air intake pipe.
3.  Start at burner and work towards Direct Vent 
termination.
4.  Remove burner cover. Loosen two screws 
securing outside air duct bracket to burner 
cover mounting plate. See Figure 22.
5.  Procure a 2-ft section of 4" diameter galvanized 
single wall vent pipe, cut off the crimped pipe 
end below stop bead.
6.  Insert one end of the vent pipe thru the outside 
air duct bracket opening and firmly push onto 
the outside air adapter collar. 
7.  Secure the pipe to collar with at least (3) 
sheet metal screws (installer provided) evenly 
spaced around the collar.
8.  Re-tighten the screws securing outside air duct 
bracket to burner cover mounting plate.
  NOTICE: 
 It is essential to ensure reliable 
operation that combustion air joints are air tight 
and that VRV is located as close to the burner as 
possible.
9.  Install supplied vacuum relief valve tee assembly, 
crimped end down, into the opposite end of vent 
pipe.
10.  Secure the tee to the pipe with at least (3) sheet 
metal screws (installer provided) evenly spaced.
11. Remove the vacuum relief valve gate assembly 
from the tee.
Figure 22: Oil Burner Installation (Beckett shown)
5 Direct Venting / Air Intake Piping (continued)
!