Specifications
50
BOILER
MODEL
GALLONS
PER HOUR GPM
PRESSURE DROP P.S.I.
AT FLOW RATE
FOR 100° F RISE
FD-7
FD-9
FD-10
FD-12
FD-14
FD-15
FD-19
FD-24
FD-30
FD-38
FD-45
300
360
420
480
540
600
720
960
1200
1440
1680
5
6
7
8
9
10
12
16
20
24
28
10.5
15.3
14.7
19.2
8.9
11.0
15.8
1.9
2.9
2.9
3.9
FD SERIES RATINGS
BOILER
MODEL
GROSS
OUTPUT
(MBH)
BOILER
H.P.
NET RATING
WATER
(MBH) (1)
BURNER INPUT
MAXIMUM
TANKLESS
HEATER
CAPACITY
GPM (3)
WATER
CONTENT
OF BOILER
(GAL.)
FURNACE
VOLUME
(CU. FT.)
APPROX. BOILER AND BURNER
SHIPPING WEIGHTS (LBS.)
OIL
(GPH) (2)
GAS
(MBH) OIL GAS GAS/OIL
FD-7
FD-9
FD-10
FD-12
FD-14
FD-15
FD-19
FD-24
FD-30
FD-38
FD-45
262
315
355
459
516
574
688
861
1090
1377
1617
7.8
9.4
10.6
13.7
15.4
17.1
20.5
25.7
32.5
41.1
48.0
229
274
309
399
449
499
598
748
948
1197
1397
2.3
2.8
3.1
4.0
4.5
5.0
6.0
7.5
9.5
12.0
14.0
331
397
447
577
649
721
865
1082
1370
1730
2019
5
6
7
8
9
10
12
16
20
24
28
44
52
80
77
94
91
87
109
153
189
177
4.8
4.8
6.0
6.0
9.2
9.2
9.2
11.4
18.8
27.6
27.6
970
1000
1080
1350
1375
1400
1560
1780
2400
3300
3560
1000
1030
1110
1380
1405
1430
1590
1810
2430
3330
3590
1020
1050
1130
1400
1425
1450
1610
1830
2450
3350
3610
1. Net ratings are based on a piping and pick-up allowance of 1.15. Consult manufacturer for installations having unusual piping and pick-up requirements,
such as intermittent system operation, extensive piping systems, etc. Ratings are for installation from sea level to 2000 feet elevation.
2. Firing rate in GPH is based on oil having a heat value of 140,000 BTU/GAL.
3. Tankless heater ratings are based on continuous draw (GAL./MIN) at 40°-140°F rise with 200°F boiler water temperature.
Note: All sizes meet or exceed 80% combustion efficiency.
STANDARD EQUIPMENT
Burnham Commercial - Lancaster, PA
Phone: 1-877-567-4328
www.burnhamcommercial.com
Specifications
ALL BOILERS
Vertical firetube type steel boiler with commercial grade 3" diameter tubes;
Insulated deluxe jacket; Pressure/temperature gauge; 30 PSI Safety relief valve;
High-Low limit control - L4081A; 750P-MT-120 (all sizes except FD7 and FD9);
OIL FIRING-Beckett Burner
Forced draft oil burner for #2 fuel oil; Burner mounted two-stage fuel pump;
Ignition transformer; Cad cell primary control; Dual oil valves; Motor voltage:
120/60/1 - all sizes
Firing sequence: On-off (FD7 thru FD19), Low-high-off (FD24 thru FD45)
GAS FIRING-Power Flame JR Series Burner
Forced draft burner for natural or LP gas; Ignition transformer; Gas pressure
regulator; Air flow safety switch and dual gas valve; RM7895A flame safeguard
control with flame rod sensor on FD7 thru FD24; RM7895A flame safeguard with
ultraviolet flame sensor FD30 thru FD45; Motor voltage: 120/60/1 - all sizes;
Firing sequence: On-off (FD7 thru FD30), Low-high-off (FD38 and FD45)
GAS/OIL FIRING-Power Flame CR Series Burner
Forced draft burner for gas/#2 fuel oil; Ignition transformer; Air flow safety switch,
dual gas valve and dual oil valves; RM7895A flame safeguard with ultraviolet
flame sensor; Gas pressure regulator and manual fuel changeover switch; Motor
voltage: 120/60/1 FD7 thru FD30, 230/60/1 FD38 thru FD45;
Firing sequence: On-off (FD7 thru FD24), Low-high-off (FD30 thru FD45)
All above are assembled, wired and packaged in a shipping crate.
RATINGS - TANKLESS COILS*
*Based on 100°F rise with 200°F boiler water temperature
and 40°F heater inlet temperature (continuous draw).
For use of the FD Series as a continuous hot water supply
boiler, select the boiler and tankless coil based on the required
amount of hot water flow. Heating needs should be consid-
ered in addition to hot water requirements. If control of hot
water temperature and flow is desired, temperature and flow
controls may be added.
Contact Burnham Commercial for inlet temperatures in excess
of 70°F, or if a temperature rise other than 100°F is desired. If
pressure drops are found to be excessive, it is possible in some
cases to oversize the heater.