Specifications
31
Boiler
Model
Boiler
HP
Burner Input
Gross
Output
(MBH)
Net
I=B=R
(MBH)
Combustion
Efficiency
Heating
Surface
(Sq. Ft.)
Furnace
Volume
(Cu. Ft.)
Press. in
Firebox
(In. W.C.)
Vent
Diam.
(In.)*
Water
Content
(Gal.)
Shipping
Weight
(Lbs.)
Oil
(GPH)
Oil
(MBH)
Gas
(MBH) Oil (%) Gas (%)
MPC4
12.7 3.5 497 500 424 369 89.0 86.3 75.0 14.5 0.10 7 63 2370
MPC5 19.5 5.5 770 773 652 567 88.8 86.1 95.3 18.0 0.19 7 78 2821
MPC6
25.0 7.1 994 995 837 728 88.7 86.0 115.5 21.6 0.28 8 93 3272
MPC7
30.6 8.7 1218 1216 1023 890 88.7 86.0 135.8 25.1 0.34 8 108 3733
MPC8 36.1 10.2 1428 1438 1209 1051 88.6 85.9 156.1 28.6 0.39 8 123 4194
MPC9 41.7 11.8 1652 1660 1395 1213 88.6 85.9 176.4 32.2 0.45 10 137 4655
MPC10 47.2 13.4 1876 1881 1580 1374 88.6 85.9 196.6 35.7 0.50 10 152 5116
MPC11
52.8 15.0 2100 2103 1766 1536 88.5 85.9 216.9 39.2 0.66 10 167 5577
MPC12
58.3 16.6 2324 2325 1951 1697 88.5 85.8 237.2 42.8 0.82 10 182 6073
MPC13 63.8 18.2 2548 2547 2137 1585 88.5 85.8 257.5 46.3 0.98 12 196 6544
MPC14 69.4 19.8 2772 2769 2322 2019 88.5 85.8 277.7 49.8 1.14 12 211 7015
MPC15 74.9 21.5 3010 2991 2508 2181 88.4 85.8 298.0 53.4 1.30 12 226 7486
MPC16 80.5 23.0 3220 3213 2694 2343 88.4 85.8 318.3 56.9 1.30 12 241 7957
MPC17 86.0 24.5 3430 3435 2880 2504 88.4 85.8 338.6 60.4 1.40 12 256 8438
MPC18 91.6 26.0 3640 3657 3065 2665 88.4 85.8 358.8 64.0 1.50 12 270 8919
Cast Iron Commercial Water or Steam Boiler
447 to 2367 MBH Input
Oil, Gas, or Oil/Gas Combination
30, 50, or 80 PSI
Cast Iron Sectional Design
Water or Steam
Top or Rear Venting
Exclusive Optional SBC
™
Boiler Control
– Maximizes System Efficiency
Series
V9