Specifications

22
Superior Quality
High Limit Control
Honeywell L4006A
High Performance
Tankless Water Heater
available in hot water
units only (optional)
Standard Equipment
All Boilers - Sections unassembled including left and right heater ends; heater opening cover plates; base-burner manifold assembly: one
assembly 5006B thru 5014B, two sub-assemblies 5015B thru 5026B; on-off firing gas control assembly; deluxe insulated jacket; rear outlet
drafthood.
Water Trim - 50 PSI safety relief valve, pressure temperature gauge, L4006A high limit control, #64 LWCO.
Steam Trim - 15 PSI safety valve, steam gauge, gauge glass set, L404A high limit control, #67 BC2 LWCO.
USA Boilers - EI- Electronic control set: one set-5006B thru 5014B, two sets-5015B thru 5026B; provides electronic ignition; 100% safety
shutoff; electronic supervision of pilot and intermittent pilot operation. Set includes: S7810M ignition control; Q348A pilot with sensing
probe; gas train for 5006 - 5009 is Robertshaw 7000 DERHC combination gas valve; gas train for 5010 - 5026 consists of dual V88A gas
valves, Q348A pilot, RV12 pilot regulator, pilot shutoff valve, main gas pressure regulator; 24V transformer furnished with all valve sets.
Canadian Boilers - Lubricated plug cock, RV-12 pilot line regulators are added to gas train. Natural Gas: Thermocouple standing pilot
assembly, 100% shut-off; one set- 5006B thru 5014B, two sets-5015B thru 5024B; EO electronic control set on 5014B (one set) and 5026B
(two sets) only; LP gas: EO electronic control set: one set-5007B thru 5014B, two sets-5015B thru 5026B.
Optional Equipment - Assembled sections; Firing sequences: low-high-off and low-high-low; Electronic control sets: EO-manual ignition,
continuous pilot flame, protecto-relay; EOP-like EO plus prewired control panel with indication lights for power on, gas valve on, flame
failure; EE-electronic ignition, intermittent pilot operation, protecto-relay; EEP-like EE plus prewired control panel with indicator lights for
power on, gas valve on, flame failure. CSD-1 and Factory Mutual components are available, consult factory.
Pressure/Temperature Gauge
Gas Controls
meet full requirements
of ANSI Z21.13
Top Supply Tappings
for ease of connection
Top Supply Tappings
for ease of connection
Front & Rear
Flue Cover Plates
easy access for inspection
and maintenance
Stainless Steel Burners
assure long life and
resist rust
Gas Train
Single gas train, 5006 thru 5014
Dual gas train, 5015 and larger
Rear Outlet Drafthood
designed specifically for
installations having