Commercial Cast Iron Boilers & Commercial Stainless Steel Condensing Boilers
Contents Product Description Fuel Range Page 399 – 800 MBH 3 Apex Boiler Stainless steel condensing water boiler Natural or LP gas Series 8H Cast iron water boiler Natural or LP gas 252 – 550 MBH 11 Series 5B Cast iron water or steam boiler Natural or LP gas 401 – 1950 MBH 19 MPC Series Multi-pass cast iron water boiler Gas, oil, or gas/oil combination 500 – 3657 MBH (3.35 – 26 GPH) 27 V9 Series Cast iron water or steam boiler Gas, oil, or gas/oil combination 447 – 2367 MBH (3.
APEX ™ Series Stainless Steel, Condensing, Gas Fired Commercial Boiler 95% Thermal Efficiency Equipped with ABC 2.
Apex Boiler Features High Performance Commercial Hydronic and Radiant Heating Introducing the Apex from Burnham Commercial, a condensing boiler with thermal efficiency ratings of 95%. The Apex utilizes a stainless steel heat exchanger, designed to extract maximum heat from the combustion process, along with the Apex Boiler Control System which is designed to enhance boiler & system efficiency and provide easy installation and servicing.
Sealed Top Panel The sealed top panel protects boiler controls from spills or leaks; the components are also isolated from the lower jacket to protect them from cold or moist combustion air Single Point Power Boiler pump and DHW pump are powered directly from the Apex Sealed Combustion with Negative Cabinet Pressure Lower portion of the boiler cabinet operates under a negative pressure, creating an additional layer of safety Smart Controls ABC 2.
Apex Boiler Control… Features Beyond Compare. The Apex Boiler Control System is the next generation of advanced electronic controls designed specifically for condensing boilers. The ABC System was designed with many features that make the control simple to understand and use, as well as features that optimize boiler performance, flexibility and overall system efficiency and reliability. The ABC System is simply the most powerful, versatile, and userfriendly boiler control available.
Ease of Connectivity… Staging and Modulation Cat 5 Connections • The ABC can be connected to external staging controls via a 4-20 mA and heat demand contact. • Enables easy connections between boilers or between boiler and building management system • External controls can modulate the boiler's firing rate in order to satisfy overall system demand. • Utilizes ordinary RJ-45 (Cat 5 Ethernet) cord • No external relays or adapters are required.
The Lower Cost, Higher Efficiency Alternative to Single Commercial Boilers Modular/Multiple Boiler Concept Modular/multiple boiler systems, such as the Apex put the efficiency, cost, and service advantages of compact gas boilers to work in heating applications where a single commercial boiler would not be sufficient. The systems connect any number of compact, self-contained gas boilers together and step-fire them to efficiently meet heating loads on demand.
System Piping TO SYSTEM The Apex is designed to be installed in a variety of configurations. Shown here are four illustrated examples of how the Apex boiler can be piped into new or existing heating systems. Examples shown here include heat-only applications, building heat plus domestic hot water, alternate piping of heat plus domestic hot water, and a multiple boiler installation incorporating domestic hot water.
Dimensions and Specifications Dimensions Model A B C D E F G H I K L M N APX399 28-7/8" 6-13/16" APX500 44-7/8" 22-1/8" APX800 54-9/10" 28-3/8" 13-11/16" 23-3/4" 15-13/16" 3/4" 1-1/2" 1-1/2" 12-1/4" 5" 8-5/16" 43-7/16" 29" 39-11/16" 29-3/8" 3/4" 1-1/2" 1-1/2" 12-1/4" 5" 7-7/16" 35" 34-1/4" 48-1/16" 33-3/16" 1" 2" 2" 12-1/4" 5" 7-1/2" 35" Low voltage knockouts (24V) Line voltage knockouts (115V) A G FPT Return Tapping O P 17-5/16" 32-7/16" 16-11/16"
Series 8H Cast Iron Gas Fired Commercial Water Boiler 252 to 550 MBH Input Over 83% Efficient 30 or 50 PSI Cast Iron Sectional Design Atmospheric Vent Modular/Multiple Boiler Configurations Available 11
Series 8H Efficient Cast Iron Commercial Water Boiler High Performance & Long Term Reliability 83% Efficiency Burnham Commercial's promise to deliver the best continues with the Series 8H. The features and efficiency of the 8H boiler make it ideal for single and multiple boiler applications. Offering space heating, or a combination of heating and domestic hot water, the Series 8H has a compact design which easily adapts to existing piping arrangements, boiler room requirements, and system heating needs.
Series 8H - Hot Water Boiler Maximum Allowable Working Pressure (MAWP): 50 PSI Safety Relief Valve Top Mounted Drafthood 50 PSI (standard) 30 PSI (optional) Blocked Vent Switch Automatically shuts down boiler in the event that the chimney or venting system become restricted.
The Lower Cost, Higher Efficiency Alternative to Single Commercial Boilers Modular/Multiple Boiler Concept Modular/multiple boiler systems put the efficiency, cost, and service advantages of compact gas boilers to work in heating applications where a single commercial boiler would not be sufficient. The systems connect any number of compact, self-contained gas boilers together and step-fire them to efficiently meet heating loads on demand.
Enjoy the Peace of Mind That Comes with Modular and Multiple Boilers Modular or Multiple? ASME Section IV differentiates between a modular and multiple boiler installation. According to ASME, a modular boiler system consists of individual modules with a maximum input of 400 MBH each. Each module is to be equipped with a pressure temperature gauge, temperature limit control, safety relief valve, and drain valve. The modules are to be manifolded together on site without any intervening stop valves.
Modular/Multiple Boiler Controls Available Controls Burnham Commercial offers a selection of system control packages to let you design modular/ multiple boiler installations based on heat use, fuel economy, and the desired level of automation. For more information on the controls shown or for more information on controls not shown here, contact Burnham Commercial. Enjoy the peace of mind that comes with modular and multiple boilers.
Recommended Modular/Multiple Boiler Selection Number of Boiler Sizes Required 805H 2 1 806H 1 2 1 807H 1 2 1 2 1 808H 1 2 1 1 2 3 2 1 4 3 2 1 3 2 1 2 1 1 809H 1 2 1 1 2 3 2 1 1 2 3 4 3 2 1 2 3 4 5 4 3 2 1 4 5 6 5 4 3 2 1 6 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 Ratings - (MBH) 810H 1 2 1 2 3 1 2 3 4 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 7 1 2 3 4 5 6 7 8 Input Gross Output Net Output Approx. Shipping Weight Lbs.
Dimensions and Specifications Boiler Model 805H 806H 807H 808H 809H 810H 'D' 'A' 20 23-3/4 27-1/2 31-1/4 35 38-3/4 'B' 10 11-7/8 13-3/4 15-5/8 17-1/2 19-3/8 'C' 7 8 9 9 10 10 USA 24-3/4 27-3/4 28-3/4 30-3/4 33-1/2 33-1/2 'E' Canada 24-3/4 25-3/4 25-3/4 26-5/8 26-3/8 26-3/8 USA 16-1/8 18 18 20 22 22 Canada 16-1/8 16 16 16 15 15 All dimensions are in inches SERIES 8H RATINGS* Natural and LP Gas BOILER MODEL (1) INPUT (MBH) GROSS OUTPUT (MBH) I=B=R NET RATING WATER (MBH) (2) 805H 806H 807H 808H 80
™ Commercial Atmospheric Gas-Fired Hydronic Heat, Hot Water or Steam Heating Capacities 401 to 1950 MBH Input 19
Series 5B - Hot Water or Steam Boiler Maximum Allowable Working Pressure (MAWP): 50 PSI-Water; 15 PSI-Steam Quality You Can Count On and lower fuel costs. Their compact design makes the sections easier to handle and assemble. Series 5B sections are easily maneuvered through standard doorways. The Burnham Commercial Series 5B boiler offers heating capacities and features that make it ideal for commercial, institutional and high rise residential heating applications.
Dimensions (in inches) BOILER MODEL 5006B 5007B 5008B 5009B 5010B 5011B 5012B 5013B 5014B 5015B 5016B 5017B 5018B 5019B 5020B 5021B 5022B 5024B 5026B JACKET OVERALL LENGTH 'A' 34 39-3/8 44-3/4 50-1/4 55-3/4 61-1/8 66-1/2 72 77-1/2 82-7/8 88-1/4 93-3/4 99-1/4 104-5/8 110 115-1/2 121 131-3/4 142-3/4 TOP SUPPLY & REAR RETURN LOCATION DRAFTHOOD HEIGHT, SIZE & LOCATION 'B' DIA.
Superior Quality Rear Outlet Drafthood designed specifically for installations having low ceilings. Top Supply Tappings for ease of connection Top Supply Tappings for ease of connection High Performance Tankless Water Heater available in hot water units only (optional) High Limit Control Honeywell L4006A Front & Rear Flue Cover Plates Pressure/Temperature Gauge easy access for inspection and maintenance Gas Controls Stainless Steel Burners meet full requirements of ANSI Z21.
Recommended Boiler Piping Water 5006 5007 5008 5009 5010 5011 5012 1-1/2" 2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 5013 5014 5015 5016 5017 5018 5019 2-1/2" 3" 3" 3" 3" 3" 3" Note: 1 supply connection & 1 return connection sizes 5006 thru 5019 5020 5021 5022 5024 5026 3" 3" 3" 3" 3" Note: 3 supply connections & 2 return connections sizes 5020 thru 5026 23
Recommended Boiler Piping Steam - Gravity Return * 1 or 2 Supply Connections - 5006 thru 5014 *Required on gravity return systems 5006 5007 5008 5009 5010 5011 5012 5013 5014 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 3" 4" 4" 4" 4" 5" 5" 5" 2" 2" 2" 2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 2" 2" 2" 3/4" 3/4" 3/4" 3/4" 1" 1" 1" 1-1/4" 1-1/4" Second supply riser optional on 5006 and 5007 24
Recommended Boiler Piping Steam - Gravity Return 5015 5016 5017 5018 5019 5020 3" 3" 3" 3" 3" 3" 4" 4" 4" 4" 4" 4" 5" 5" 5" 5" 5" 5" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2-1/2" 2" 2" 2" 2" 2" 2" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 1-1/4" 3 supply connections boiler sizes 5015 thru 5020 * Required on gravity return systems * 5021 5022 5024 5026 3" 3" 3" 3" 4" 4" 4" 4" 5" 5" 5" 5" 6" 6" 6" 6" 2-1/2" 2-1/2" 2-1/2" 3" 2" 2" 2" 2-1/2" 1-1/2"
Specifications SERIES 5B RATINGS RATINGS MBH (2) (3) BOILER MODEL (1) 5006B 5007B 5008B 5009B 5010B 5011B 5012B 5013B 5014B 5015B 5016B 5017B 5018B 5019B 5020B 5021B 5022B 5024B 5026B WATER GROSS I=B=R INPUT OUTPUT MBH 401 468 546 624 702 780 858 936 1014 1092 1170 1248 1326 1404 1482 1560 1638 1794 1950 321 375 437 500 562 624 687 749 812 874 936 999 1061 1124 1186 1248 1311 1436 1560 RECOMMENDED CHIMNEY SIZE (6) NET RATINGS (4) (5) 279 326 380 434 488 543 597 651 705 760 814 868 922 977 1031 1085 113
MPC High Efficiency Cast Iron Multi-Pass Commercial Water Boiler Up to 89% efficient! Unsurpassed thermal shock protection Innovative plug & play integrated boiler operating controls Commercial-grade, 3-pass sections, utilizing Burnham Commercial’s exclusive BC25-HSi cast iron From 4 to 18 sections, rated at 500,000 to 3.
MPC Multi-Pass Commercial Boiler All New from Top to Bottom with Industry Leading Technology Take one look at the MPC™, Multi-Pass Commercial boiler, and there is no question that it is setting new standards for cast iron commercial boilers.
SBC ™ MENU Integrated Boiler Control System The Burnham Commercial SBC is a complete boiler monitoring and automation system. Available as an option, this exclusive feature was designed and developed by Burnham Commercial engineers and is available ONLY on Burnham Commercial products.
MPC Engineered to Outperform All Other Cast Iron Commercial Boilers Specifications Certified for use in Canada Minimum return water temperature: 80ºF Minimum supply water temperature: 130ºF Maximum Delta T: 80ºF Boiler Model MPC4 MPC5 MPC6 MPC7 MPC8 MPC9 MPC10 MPC11 MPC12 MPC13 MPC14 MPC15 MPC16 MPC17 MPC18 Boiler HP 12.7 19.5 25.0 30.6 36.1 41.7 47.2 52.8 58.3 63.8 69.4 74.9 80.5 86.0 91.6 Burner Input Oil (GPH) 3.5 5.5 7.1 8.7 10.2 11.8 13.4 15.0 16.6 18.2 19.8 21.5 23.0 24.5 26.
V9 Series Cast Iron Commercial Water or Steam Boiler 447 to 2367 MBH Input Oil, Gas, or Oil/Gas Combination 30, 50, or 80 PSI Cast Iron Sectional Design Water or Steam Top or Rear Venting Exclusive Optional SBC™ Boiler Control – Maximizes System Efficiency 31
V9 Series Cast Iron Commercial Water or Steam Boiler Your Commercial Heating Solution! Installation & Service Flexibility Available in ten sizes with gross output ratings from 347 to 1900 MBH, the V9 Series fires gas, oil or combination gas/oil and is available equipped with either steam or water trim. The product meets the energy efficiency requirements of ASHRAE 90.1 with combustion efficiencies up to 86%.
V9 Series - Hot Water or Steam Boiler Maximum Allowable Working Pressure (MAWP): 80 PSI-Water; 15 PSI-Steam Top or Rear Outlet Front Mounted Controls with adjustable lock-type damper (not shown); includes plugged tapping for outlet pressure readings for easy adjustment and maintenance Removable Side Jacket Panels Easy access to all cleanouts Cast Iron Vertical Design with pinned heating surface for maximum heat extraction Optional Tankless Heater Provides domestic hot water Burner Mounting Plate Rea
SBC™ Boiler Control System Exclusive Optional Feature for Burnham Commercial Boilers SBC Integrated Boiler Control System The Burnham Commercial SBC is a complete boiler monitoring and automation system. Available as an option, this exclusive feature was developed by Burnham Commercial engineers and is designed specifically for use on Burnham Commercial boilers.
V9 Series Dimensions BURNER MOUNTING PLATE/ BURNER DIMENSION* # OF BOILER # OF STEAM MODEL SECTIONS 'A' 'B' RISERS V903A 3 18-1/4 12 1 V904A 4 24-1/4 18 1 V905A 5 30-1/4 24 1 V906A 6 36-1/4 30 1 V907A 7 42-1/4 36 2 V908A 8 48-1/4 42 2 V909A 9 54-1/4 48 2 V910A 10 60-1/4 54 2 V911A 11 66-1/4 60 2 V912A 12 72-1/4 66 3 BECKETT 'C' — — — — — — — — — 30 'D' 9-1/8 12-1/8 15-1/8 18-1/8 21-1/8 24-1/8 27-1/8 30-1/8 33-1/8 36-1/8 CARLIN MAX. FLUE HEATERS OUTLET 'CF' 'CG' 'E' DIA.
V9 Series Piping Recommendations Water and Steam WATER BOILER PIPING To be used when system return water is not less than 135° F for prolonged periods of time and system flow does not impact flow through the boiler RETURN PIPING SIZE (IN.) SUPPLY PIPING SIZE (IN.
V9 Series Burner Schedule V9 Series Burners OIL BURNERS OIL BURNERS BECKETT CARLIN POWER FLAME WEBSTER BOILER MODEL BURNER MODEL H.P. BURNER MODEL H.P. BURNER MODEL H.P. BURNER MODEL H.P.
V9 Series Ratings & Equipment Listing NET I=B=R RATINGS (2) (3) BOILER MODEL (1) BOILER H.P. GROSS OUTPUT MBH (2) V-903A V-904A V-905A V-906A V-907A V-908A V-909A V-910A V-911A V-912A 10.3 14.4 19.3 24.1 28.6 33.2 40.1 45.6 51.2 56.8 347 483 646 808 959 1110 1342 1528 1714 1900 STEAM BURNER INPUT MBH SQ. FT. WATER MBH OIL (GPH) (4) 260 362 485 606 719 833 1014 1168 1323 1474 1083 1508 2021 2525 2996 3471 4225 4867 5513 6142 302 420 562 703 834 965 1167 1329 1490 1652 3.1 4.2 5.6 7.0 8.3 9.
V11 Series Cast Iron Commercial Water or Steam Boiler 837 to 5733 MBH Input Oil, Gas, or Oil/Gas Combination 30, 50, or 80 PSI Cast Iron Sectional Design Water or Steam Top or Rear Venting Exclusive Optional SBC Boiler Control™ – Maximizes System Efficiency 39
V11 Series Cast Iron Commercial Water or Steam Boiler Your Commercial Heating Solution! Available in twenty sizes with gross output ratings from 667 to 4551 MBH, the V11 Series is commonly used in schools, hospitals, and other large commercial applications where comfort and reliability are critical. The product meets the energy efficiency requirements of ASHRAE 90.1 with combustion efficiencies up to 85%.
Commitment to Quality Burnham Commercial, "America's Boiler Company," has earned a reputation for quality and dependability. Built for a variety of applications, the V11 Series is right for your next job.
V11 Series Dimensions BURNER DIMENSION - 'M' * BOILER MODEL V1104 V1105 V1106 V1107 V1108 V1109 V1110 V1111 V1112 V1113 V1114 V1115 V1116 V1117 V1118 V1119 V1120 V1121 V1122 V1123 NUMBER OF SECTIONS 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 BECKETT 'A' 26-5/8 32-3/4 38-7/8 45 51-1/8 57-1/4 63-3/8 69-1/2 75-5/8 81-3/4 87-7/8 94 100-1/8 106-1/4 112-3/8 118-1/2 124-5/8 130-3/4 136-7/8 143 'B' 18-7/8 25 31-1/8 37-1/4 43-3/8 49-1/2 55-5/8 61-3/4 67-7/8 74 80-1/8 86-1/4 92-3/8 98-1/2 104-5/8 110-3/
V11 Series Piping Recommendations Water Boiler Gas Boilers Pipe Sizing and Notes NOTES: 1. All piping is schedule 40. 2. Pipe size listed are based on a 20° F or 40° F differential (temperature drop). Select one to match application. 3. When specified return piping size is less than 3", install 3" x 12" nipple and appropriate size bell reducer directly into boiler return tapping as shown. 4.
V11 Series Piping Recommendations Steam Boiler PIPING SIZE IN INCHES (1) RISER BOILER (2) (3) (4) MODEL (QTY.
V11 Series Burner Schedule OIL BURNERS BECKETT CARLIN POWER FLAME WEBSTER BOILER NUMBER BURNER MODEL H.P. BURNER MODEL H.P. BURNER MODEL H.P. BURNER MODEL H.P.
Specifications V11 RATINGS BOILER MODEL (1) V1104 V1105 V1106 V1107 V1108 V1109 V1110 V1111 V1112 V1113 V1114 V1115 V1116 V1117 V1118 V1119 V1120 V1121 V1122 V1123 GROSS OUTPUT MBH BOILER H.P. (2) 19.9 667 25.6 857 31.9 1069 38.3 1281 45.3 1517 51.7 1729 1941 58.0 2154 64.3 69.7 2334 74.8 2503 81.6 2730 88.3 2957 93.4 3129 100.2 3353 3580 106.9 3739 111.7 3957 118.2 4174 124.7 129.5 4334 136.
Commercial Hydronic Heat Pressure-Fired Steel Boiler Oil, Gas or Combination Hot Water Heating Heating Capacities 262 to 1617 MBH Output 47
FD Series - Steel Firetube, Hot Water Boiler Maximum Allowable Working Pressure (MAWP): 30 PSI-Water Versatility at Its Best FD Series boilers are available with oil, gas or gas/ oil burners. As a forced draft boiler, the FD Series eliminates the need for external draft devices, such as a high chimney or mechanical draft equipment. The vertical design of the FD Series provides a smaller footprint per gross output than conventional boilers of comparable ratings.
Dimensions Dimensions (in inches) BOILER MODEL NUMBER FD-7 FD-9 'A' - Boiler Width/Length 28 28 32 32 35 35 35 49-7/8 55-7/8 56 56 61 61 61 Oil 36-3/4 36-3/4 41 41 Gas 47-1/4 47-1/4 51-1/2 51-1/2 54-3/4 54-3/4 54-3/4 'B' - Inspection & Alternate Supply Connection Height 'C' - Boiler Length (including buner) FD-10 FD-12 FD-14 FD-15 FD-19 FD-24 FD-30 FD-38 FD-45 Gas/Oil 57 57 38 44-1/2 48 48 61-1/4 65-1/8 71-1/4 71-1/4 44-1/4 44-1/4 55-1/4 58-1/4 66-1/4 68-1/2 68-1/2 61-1/2
Specifications FD SERIES RATINGS MAXIMUM APPROX. BOILER AND BURNER TANKLESS WATER SHIPPING WEIGHTS (LBS.) HEATER CONTENT FURNACE GROSS NET RATING CAPACITY OF BOILER VOLUME BOILER OUTPUT BOILER OIL GAS WATER GPM (3) MODEL (MBH) H.P. (MBH) (1) (GPH) (2) (MBH) (GAL.) (CU. FT.) OIL GAS GAS/OIL 1020 229 1000 2.3 4.8 FD-7 262 7.8 331 5 44 970 1050 274 1030 2.8 4.8 315 9.4 397 52 1000 FD-9 6 1130 309 1110 3.1 6.0 355 10.6 447 1080 FD-10 7 80 1400 399 1380 4.0 6.0 459 13.7 1350 FD-12 577 8 77 1425 449 1405 4.5 9.
Limited Warranty FD SERIES Limited Warranty – Except as provided below with respect to products or parts not manufactured by Burnham Commercial, Burnham Commercial warrants to the original owner at the original installation site that products manufactured by Burnham Commercial, America’s Boiler Company comply, at the time of manufacture, with recognized Hydronics industry regulatory agency standards and requirements then in effect and will be free from defects in materials and workmanship for a period of o
For Commercial Grade Boilers Limited Warranty Using Cast Iron, Carbon Steel, or Stainless Steel Heat Exchangers and Parts / Accessories Subject to the terms and conditions set forth below, Burnham Commercial, Lancaster, Pennsylvania hereby extends the following limited warranties to the original owner of a commercial grade water or steam boiler or Burnham Commercial supplied parts and/or accessories manufactured and shipped on or after October 1, 2009: ONE YEAR LIMITED WARRANTY ON COMMERCIAL GRADE BOILE
Burnham Commercial P.O. Box 3939, Lancaster, PA 17604 888-791-3790 www.burnhamcommercial.