Alpine Data Sheet

©2017U.S.BoilerCompany,Inc.-Lancaster,PA
Phone:1-888-432-8887
PrintedintheU.S.A.
FormNo.HYDL0408110Ms
www.usboiler.net
Alpine: Technical Information
Alpine Ratings & Specications (sea level to 2000 feet)
Model AFUE%
Input
(MBH)
min-max
DOE
Heating
Capacity
(MBH)
Net AHRI
(MBH)
Vent Size
(Inches)
Approx.
Shipping
Weight.
(lbs.)
MODELSFORWALLORFLOORMOUNTING
ALP080B 95.0 16-80 72 63 3 137
ALP105B 95.0 21-105 96 83 3 155
ALP150B 95.0 30-150 136 118 3 182
ALP210B 95.0 42-210 194 169 3 206
FLOORMOUNTEDMODELS
ALP285B 95.0 57-285 262 228 4 256
ALP399C 94.1
1
80-399 375
2
326
3
4 316
Alpine Residential Standard Equipment
• Directventappliance
• Nylonfloorguides
• Pre-installedhangingbracketandwallmountkitincluded
• Gas,water,electricalconnectionsonleftsideofboiler
• Slide-outcontrolpanel
• Slide-outlinevoltageterminalstrip
• Sage2.2ControlSystem
–LCDtouchscreendisplay
–Self-guidedcontrolmenus
–100+helpscreens
–Built-inselfdiagnostics
–(3)separatecirculatoroutputs
–Built-insequencer,stagesupto(8)boilers
–4-20MVinputsforexternalcontrol
–Outdoorresetincludingwiredoutsidesensor
–DHWpriority
–Warmweathershutdown
• Variablespeedcombustionblower
• NaturalorLPgas
• Negativepressuregasvalve
• Stainlesssteelheatexchanger
• Boilerloopcirculator
• Polypropylenecondensatetrapw/overflowprotection
• Supply,return,andautoresethighlimitwatersensors
• 30PSIsafetyreliefvalve
• Temperatureandpressuregauge
• Fluegastemperaturesensoranddifferentialpressureswitch
• CPVCtoPVCventkit
–Includes30”CPVC,90°elbow,2-ventterminals,screens,
• Fiveyearpartsreplacementwarranty
A
S
M
E
H
16-11/16”
A
Low Voltage
Knockouts (24V)
Line Voltage
Knockouts (115V)
One handle on
ALP80 & 105, Two
handles on all
other models
G
(Return tapping)
F
(Gas valve inlet)
H
(Supply tapping)
3/4” FPT
relief/drain
tapping
J
(Condensate
trap drain)
Wall Mount
Bracket (included
on ALP80-210)
7-3/16”
Floor mounted
models only
(ALP285-399)
12-1/4”
6-1/4”
M
Alpine Vent & Intake Sizes
Model
Intake
Size
Vent
Size
Max Length
Intake/Vent
ALP080B
2” 2” 60’/60’
3” 3” 135’/135’
ALP105B
2” 2” 60’/60’
3” 3” 135’/135’
ALP150B 3” 3” 135’/135’
ALP210B 3” 3” 135’/135’
ALP285B
3” 3” 60’/60’
4” 4” 100’/100’
ALP399 4” 4” 100’/100’
1
Thermalefficiency
Alpine Dimensions (inches)
Model A F G H M
ALP080B 12-9/16 1/2 1 1 32-3/16
ALP105B 14 1/2 1 1 32-3/16
ALP150B 19-11/16 1/2 1 1 32-3/16
ALP210B 23-15/16 1/2 1 1 32-3/16
ALP285B 21-13/16 3/4 1-1/4 1-1/4 43-7/16
ALP399 28-7/8 3/4 1-1/2 1-1/2 43-7/16
NOTES:
DOEHeatingCapacity(ALP080throughALP285);GrossOutput(ALP399)
SafetyReliefValvePressure,Water(ALP080BthruALP285B)–30PSIstd.;
50PSI,80PSI,and100PSIoptional
SafetyReliefValvePressure,Water(ALP399only)-50PSIstd.;
80PSIand100PSIoptional
ASMEcertified150PSIMaximumAllowableWorkingPressureat210ºF.
Maxallowabletemperaturesetting210ºF
Targetsetpointis190°F,automaticresethighlimitsetpointis200°Fand
manualresethighlimitsetpointis210°F
Boilersshippedsetfornaturalgas;fieldadjustmentforLP(seeinstructionmanual)
Forelevationsabove2000feet,reduceratingsfourpercent(4%)
per1000feetabovesealevel
2
Grossoutput
3
Netrating
Optional Equipment:
• LWCOkit(P/N:100592-01)
• SageZoneControl
–CirculatorPanel(P/N:104590-01)
–ValvePanel(P/N:104589-01)
• Servicepartsrepairkit
(P/N:105319-04)
Additionalapprovedoptions
C