Operating instructions
58
I.  Check pilot burner ame and main burner ames 
through observation port.
1.  Check pilot ame. Refer to Table 11 for appropriate 
pilot detail.
2.  Adjust thermostat to highest setting.
3.  Check main burner ames. See Figure 52. Flame 
should have clearly dened inner cones with no 
yellow tipping. Orange-yellow streaks caused 
by dust should not be confused with true yellow 
tipping.
  Yellow-tipping indicates lack of primary air. 
Improper burner alignment on Main Burner Orice 
will also affect primary air injection. Adjust primary 
air as follows:
Figure 49: Honeywell Q348 Pilot Flame
(24V Electronic Ignition)
Figure 48: Honeywell Q314 Pilot Flame
(24V Standing Pilot)
Figure 50: Honeywell Q179D Pilot Flame (OP)
Figure 51: Honeywell Q179C Pilot Flame (EP)
Figure 52: Main Burner Flame