Installation Operating Instructions
42
(18) Clearances to combustible material – use of
thimbles.
(19) Firestops.
(20) Flashing and storm collars.
(21) Guying or bracing of common vent pipe above
roof.
(22) Securing and gas tightness of joints.
(23) Lightning arrester if top of metal vent is one of
highest points on the roof.
Where choice is possible, many advantages can be
listed for the UL Listed double wall metal type B vent:
1. Warm up is faster with type B vents than vents
having greater mass.
2. Type B vents permit closer clearance to
combustible material than single wall metal
vents unless special precautions are taken with
the latter.
3. Type B vents are less prone to condensation and
corrosion than single wall metal vents.
4. Type B vents are lightweight, easy to handle and
assemble.
SECTION III – INSTALLATION INSTRUCTIONS (continued)
WHEN AN EXISTING BOILER IS REMOVED FROM A COMMON VENTING SYSTEM, THE COMMON VENTING
SYSTEM IS LIKELY TO BE TOO LARGE FOR PROPER VENTING OF THE APPLIANCES REMAINING CONNECTED
TO IT. AT THE TIME OF REMOVAL OF AN EXISTING BOILER, THE FOLLOWING STEPS SHALL BE FOLLOWED
WITH EACH APPLIANCE REMAINING CONNECTED TO THE COMMON VENTING SYSTEM PLACED IN OPERATION,
WHILE THE OTHER APPLIANCES REMAINING CONNECTED TO THE COMMON VENTING SYSTEM ARE NOT
IN OPERATION.
A.
SEAL ANY UNUSED OPENINGS IN THE COMMON VENTING SYSTEM.
B.
VISUALLY INSPECT THE VENTING SYSTEM FOR PROPER SIZE AND HORIZONTAL PITCH AND DETERMINE
THERE IS NO BLOCKAGE OR RESTRICTION, LEAKAGE, CORROSION AND OTHER DEFICIENCIES WHICH
COULD CAUSE AN UNSAFE CONDITION.
C.
INSOFAR AS IS PRACTICAL, CLOSE ALL BUILDING DOORS AND WINDOWS AND ALL DOORS BETWEEN
THE SPACE IN WHICH THE APPLIANCES REMAINING CONNECTED TO THE COMMON VENTING SYSTEM
ARE LOCATED AND OTHER SPACES OF THE BUILDING. TURN ON CLOTHES DRYER AND ANY APPLIANCE
NOT CONNECTED TO THE COMMON VENTING SYSTEM. TURN ON ANY EXHAUST FANS, SUCH AS
RANGE HOODS AND BATHROOM EXHAUSTS, SO THEY WILL OPERATE AT MAXIMUM SPEED. DO NOT
OPERATE A SUMMER EXHAUST FAN. CLOSE FIREPLACE DAMPERS.
D.
PLACE IN OPERATION THE APPLIANCE BEING INSPECTED. FOLLOW THE LIGHTING INSTRUCTIONS.
ADJUST THERMOSTAT SO APPLIANCE WILL OPERATE CONTINUOUSLY.
E.
TEST FOR SPILLAGE AT THE DRAFT HOOD RELIEF OPENING AFTER 5 MINUTES OF MAIN BURNER
OPERATION. USE THE FLAME OF A MATCH OR CANDLE, OR SMOKE FROM A CIGARETTE, CIGAR OR
PIPE.
F.
AFTER IT HAS BEEN DETERMINED THAT EACH APPLIANCE REMAINING CONNECTED TO THE COMMON
VENTING SYSTEM PROPERLY VENTS WHEN TESTED AS OUTLINED ABOVE, RETURN DOORS, WINDOWS,
EXHAUST FANS, FIREPLACE DAMPERS AND OTHER GAS BURNING APPLIANCE TO THEIR PREVIOUS
CONDITIONS OF USE.
G.
ANY IMPROPER OPERATION OF THE COMMON VENTING SYSTEM SHOULD BE CORRECTED SO THE
INSTALLATION CONFORMS WITH THE NATIONAL FUEL GAS CODE, ANSI Z223.1. WHEN RESIZING ANY
PORTION OF THE COMMON VENTING SYSTEM, THE COMMON VENTING SYSTEM SHOULD BE RESIZED
TO APPROACH THE MINIMUM SIZE AS DETERMINED USING THE APPROPRIATE TABLES IN CHAPTER
10 IN THE NATIONAL FUEL GAS CODE, ANSI Z223.1.