User guide

32
Electrical connection
10.5. Electrical installation AS-Interface
A detailed description of the bus communication can be
found in the operating instructions Type 8791.
10.5.1. Connection with circular plug-in
connector M12 x 1, 4-pole, male
Connector views
The views show the image from the front looking at the pins, the
solder connections are behind them.
Pin 4:
NC
Pin 1:
Bus +
Pin 3:
Bus –
Pin 2:
NC
Fig. 22: Bus connection without external supply voltage
Pin 4:
24 V +
Pin 1:
Bus +
Pin 3:
Bus –
Pin 2:
GND
Fig. 23: Bus connection with external supply voltage (optional)
Bus connection without external / with external supply voltage
Pin Designation Configuration
1
Bus + AS Interface bus line +
2
NC or GND
(optional)
not used or external supply voltage –
(optional)
3
Bus – AS Interface bus line –
4
NC or 24 V +
(optional)
not used or external supply voltage +
(optional)
Tab. 20: Pin assignment of circular plug-in connector for AS-Interface
When the supply voltage is applied, the positioner is operating.
Actuate the automatic adjustment of the positioner, as described
in the chapter entitled “11.2. Specifying the standard settings”.
10.5.2. Programming data AS-Interface
Version Profile S-7.3.4 Version Profile S-7.A.5
I/O con-
figuration
7 hex 7 hex
ID code 3 hex (analog profile) A hex
Extended
ID code 1
F hex (Default value, can
be changed by the user)
7 hex
Extended
ID code 2
4 hex 5 hex
Profile S-7.3.4 S-7.A.5
Tab. 21: Programming data
english
Type 8791