User guide

31
Electrical connection
10.4.3. Terminal assignment for output
signals to the control centre (e.g. PLC)
- (required for analogue output option
only)
Terminal Configuration On the
device side
External circuit / Signal
level
31 + Analogue
feedback +
31 +
+ (0/4 – 20 mA)
not galvanically isolated
32 –
Analogue
feedback GND
32 –
GND (identical with the
GND supply voltage)
Tab. 16: Terminal assignment; output signals to the control centre
10.4.4. Terminal assignment for operating
voltage
Terminal Configuration External circuit / Signal level
+24 V
Operating
voltage +
24 V DC ± 10 %
max. residual ripple 10%
+24 V
GND
GND
Operating
voltage GND
Tab. 17: Terminal assignment; operating voltage
10.4.5. Terminal assignment for connecting
the external position sensor (for remote
model only)
Terminal Configuration
On the
device side
External circuit / Signal
level
S +
Supply
sensor +
S +
+
Remote
Sensor
Type
8798
8)
S –
Supply
sensor –
S – –
A
Serial interface,
A cable
A A-line
B
Serial interface,
B-cable
B B-line
8) Assignment of the wire color see “Tab. 19”
Tab. 18: Terminal assignment; external position sensor
Positioner
Terminal
Wire color Remote
Sensor with cable
type 1
Wire color Remote
Sensor with cable
type 2
S + brown brown
S – white black
A green red
B yellow orange
Tab. 19: Assignment of the wire color (Remote Sensor)
english
Type 8791