User guide

22
Attachment and assembly
8.3.1. Installation
WARNING!
Risk of injury from improper installation!
Installation may be carried out by authorised technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
an uncontrolled restart!
Secure system from unintentional activation.
Following assembly, ensure a controlled restart.
Procedure:
Specify the attachment position of the positioner:
- parallel to the actuator or
- rotated by 90° to the actuator.
Determine home position and direction of rotation of the actuator.
Anti-twist safeguard:
Note the flat side of the axle!
One of the setscrews must be situated on the flat side of the
axle as an anti-twist safeguard (see “Fig. 12”).
Connect adapter to the axle of the positioner and secure with
2 setscrews.
Secure setscrews with self-locking nuts to prevent them from
working loose.
Angular range of the position sensor:
The maximum angular range of the position sensor is 180°.
The axle of the positioner may be moved within this range
only.
90°
Ideal position for the angular
range of the positioner = 90°
(min. 30° / max. 180°)
The rotational movement of the
rotary actuator must be within
the position sensor rotational
range of 180°.
Flattened axle
180°
Maximum
rotational range
Fig. 12: Angular range / anti-twist safeguard