Electrical connection
13.3.4. Terminal assignment for output signals to the control
centre (e.g. PLC) (required for analogue output option only)
Terminal Configuration On the device side External circuit / Signal level
31 + Analogue feedback +
31 +
+ (0/4 – 20 mA)
not galvanically isolated
32 – Analogue feedback GND
32 –
GND (identical with the GND supply
voltage)
Table 27: Terminal assignment; output signals to the control centre
13.3.5. Terminal assignment for operating voltage
Terminal Configuration External circuit / Signal level
+24 V Operating voltage +
+24 V
GND
24 V DC ± 10%
max. residual ripple 10%
GND Operating voltage GND
Table 28: Terminal assignment; operating voltage
13.3.6. Terminal assignment for external position sensor
(for remote model only)
Terminal Configuration On the device side External circuit / Signal level
S + Supply sensor +
S +
+
Remote-
Sensor
Type 8798
11)
S - Supply sensor –
S –
A Serial interface, A cable
A
A line
B Serial interface, B-cable
B
B line
11) Assignment of the wire color see “Table 30”
Table 29: Terminal assignment; external position sensor
Positioner
Terminal
Wire color
Remote-Sensor with cable type 1
Wire color
Remote-Sensor with cable type 2
S + brown brown
S – white black
A green red
B yellow orange
Table 30: Assignment of the wire color (Remote-Sensor)
english
Type 8791