Owner manual

52
Electrical connection
13.3. Electrical connection with cable gland
13.3.1. Designation of the screw-type terminals
11 +
12 –
81
82
31 +
32 –
A
B
+
+24 V
GND
remote sensor
Figure 26: Designation of the screw-type terminals
13.3.2. Connection of the screw-type terminals
Unscrew the 4 screws on the housing cover and remove the cover.
The screw-type terminals are now accessible.
Connect terminals according to the configuration.
13.3.3. Terminal assignment for input signals from the control
centre (e.g. PLC)
Terminal Configuration On the device side External circuit / Signal level
11 + Set-point value +
11 +
+ (0/4 – 20 mA)
not galvanically isolated
12 – Set-point value GND
12 –
GND set-point value
81 + Binary input +
81 +
+
0 – 5 V (log. 0)
10 – 30 V (log. 1)
82 – Binary input –
82 –
GND (identical with the GND supply
voltage)
Table 26: Terminal assignment; input signals of the control centre
english
Type 8791