Attachment and assembly
11.4.2. Connection and start-up of the Remote-Sensor Type 8798
WARNING!
Risk of injury from improper start-up!
• Start-up may be carried out by authorised technicians only and with the appropriate tools!
Risk of injury from unintentional activation of the system and an uncontrolled restart!
• Secure system from unintentional activation.
• Following assembly, ensure a controlled restart.
→ Connect the 4 wires of the sensor cable to the designated screw-type terminals of the positioner
(see chapter “13.3.6. Terminal assignment for external position sensor
(for remote model only)”).
→ Attach remote sensor on the actuator.
The correct procedure is described in the brief instructions for the remote sensor.
→ Connect positioner pneumatically to the actuator.
→ Connect compressed air to positioner.
→ Switch on supply voltage to the positioner.
→ Run the X.TUNE function.