Technical Data
8.8. Factory settings of the positioner
8.8.1. Functions can be activated via DIP switches
Function Parameter Value
CUTOFF
Sealing function below
Sealing function above
2 %
98 %
CHARACT
Select characteristic FREE
DIR.CMD
Effective direction set-point value increasing
Table 5: Factory settings; Functions can be activated via DIP switches
8.8.2. Functions can be activated via communications software
Function Parameter Value
INPUT
Set-point value input 4 – 20 mA
DIR.ACTUATOR
Effective direction actual value increasing
SPLITRANGE
Signal split range below
Signal split range above
0 %
100 %
X.LIMIT
Function deactivated
Stroke limit below
Stroke limit above
0 %
100 %
X.TIME
Function deactivated
Actuating time Open
Actuating time Closed
(1 s) values determined by X.TUNE
(1 s) values determined by X.TUNE
After implementation of RESET: 1 s
X.CONTROL
Dead band
Open amplification factor
Close amplification factor
1,0 %
(1) values determined by X.TUNE
(1) values determined by X.TUNE
After implementation of RESET: 1
SAFEPOSITION
Safety position 0 %
SIGNAL ERROR
Sensor break detection set-point value OFF
BINARY INPUT
Function active
Binary input function
Operating principle of binary input
Safety position
Normally open contact
OUTPUT
Function active
Norm signal output: Parameter
Norm signal output: Type
Position
4 – 20 mA
Table 6: Factory settings; Functions can be activated via communications software
english
Type 8791