Owner's manual
91
2.5.4. Parameters that can be displayed or modified by channels
Name Value
Unit Status
# # Channel 0
Channel enable enable
- Initial valueBehavior at CPU/Master-STOP switching alternative value
Alternative value 0
# # # Pilot valve
Switching cycle counter reset inactive
-
Initial value
ID number of the pilot valve 0 Initial value
Current number of the switching cycles 74766 -
# # # Actuator
Enable switching cycle counter diagnosis enable
-
Initial value
Switching cycle counter warning limit 0
Switching cycle counter reset inactive
Date of the last switching cycle counter reset -
Current number of switching cycles 74766 -
# # # Diagnosis
Group diagnosis
barred
- -
Broken wire
Short circuit
2.5.5. Functions of the channel parameter (general)
• Enable channel (read / write)
Defines whether or not the channel is enabled for use.
• Behavior at CPU/Master STOP (read / write)
Defines which value the channel assumes when the master is set to STOP.
• Alternative values (read / write)
Defines the alternative value for the case „Switch alternative value at master STOP“.
2.5.6. Functions of the parameter actuator (that are connected to
the pilot valve (of this channel)
• Switching cycle counter reset
Initiates a reset of the actuator switching cycle counter.
• ID number of the pilot valve (read / write)
You can enter the ID number of the pilot valve used here. This makes it quickly available if replacement or pre-
ventive maintenance are forthcoming.
• Current number of switching cycles (read only)
Indicates how many switching cycles the pilot valve has performed since the last counter reset.
Type 8650
english
Commissioning