Owner's manual

91
2.5.4. Parameters that can be displayed or modified by channels
Name Value
Unit Status
# # Channel 0
Channel enable enable
- Initial valueBehavior at CPU/Master-STOP switching alternative value
Alternative value 0
# # # Pilot valve
Switching cycle counter reset inactive
-
Initial value
ID number of the pilot valve 0 Initial value
Current number of the switching cycles 74766 -
# # # Actuator
Enable switching cycle counter diagnosis enable
-
Initial value
Switching cycle counter warning limit 0
Switching cycle counter reset inactive
Date of the last switching cycle counter reset -
Current number of switching cycles 74766 -
# # # Diagnosis
Group diagnosis
barred
- -
Broken wire
Short circuit
2.5.5. Functions of the channel parameter (general)
Enable channel (read / write)
Defines whether or not the channel is enabled for use.
Behavior at CPU/Master STOP (read / write)
Defines which value the channel assumes when the master is set to STOP.
Alternative values (read / write)
Defines the alternative value for the case „Switch alternative value at master STOP“.
2.5.6. Functions of the parameter actuator (that are connected to
the pilot valve (of this channel)
Switching cycle counter reset
Initiates a reset of the actuator switching cycle counter.
ID number of the pilot valve (read / write)
You can enter the ID number of the pilot valve used here. This makes it quickly available if replacement or pre-
ventive maintenance are forthcoming.
Current number of switching cycles (read only)
Indicates how many switching cycles the pilot valve has performed since the last counter reset.
Type 8650
english
Commissioning