User guide


English
8645 - 69


(x10) (x1)Baud rate
 The rotary encoder switch is located in the lower part
of the DeviceNet fieldbus module (see illustration Rotary Encoder
Switch).

Addresse 1 0 (x10) + 1 (x1)
: : :
Addresse 6 6 (x10) +  (x1)

Value Baud rate
0 125 kBaud
1 250 kBaud
2 500 kBaud
Illustration: Rotary encoder switch

BUS_OK (BO)
FAILURE_SELECT (FS)
U_LOGIK_OK (U
l
)
U_SENSOR_OK (U
S
)
BUS_FAULT (BF)
FAILURE_NUMBER (FN)
U_DRIVER_OK (U
O
)


BUS (BO)
BUS (BF)
FS
FN
U
o
U
i
U
S
ON
OFF
OFF
OFF
ON
ON
ON
Illustration: Allocation of the LED’s on the Field bus module DeviceNet

   
BO green BUS STATUS See condition of the BUS STATUS LEDs
BF red BUS STATUS See condition of the BUS STATUS-LEDs
FS yello FAILURE
SELECT
Defines the function of the LED FN:
FS lit: FN indicates the type of failure
FS not lit: FN indicates the failure number
FN red FAILURE
NUMBER
The number of flashing pulses indicates the failure type or fai-
lure number, depending on if FS is lit or not.
U
i
green U Logik OK Voltage for logic supply,
Inputs and bus interface provided.
U
O
green U DRIVER OK Power supply for the outputs available.
U
S
green U Sensor OK Separate display of the voltage for the inputs.