User guide
English
8645 - 5
BUS (BO) OFF
Response monitoring time on
FreeLINE has expired.
The master has not responded.
Check network configuration at master
(controller) and station address of the
valve cluster.
Check master (controller) and bus
cable.
BUS (BF) ON
FS OFF
FN OFF
U
i
ON
U
O
ON
U
S
ON
BUS (BO) OFF The fieldbus module is ready for the
status “Data Exchange”, but the
master sends no Global Control
Operate telegram [e.g. if the PLC is at
Stop (Global Control Clear)].
This status does not represent an
error. The function can, however, be
bypassed in the parameter telegram
(see chapter Commissioning).
BUS (BF) FLASHING
FS OFF
FN OFF
U
i
ON
U
O
ON
U
S
ON