The task of the bus system is the high-speed serial connection of decentralized peripheral elements with the
central master (controller). Diagnostic data is transmitted in addition to the input / output data.
DeviceNet-Master (controllers) requires a configuration program. This program requires an Electronic Data
Sheet (EDS) file containing bus-specific data.

Available baud rates 125 / 250 / 500 kbaud
Data volume without RIO expansion 2 input and 2 output bytes
Data volume with RIO 8645 expansion or
intermediate module
2 input and 2 output bytes per expansion
Data volume with RIO 8640 4 input and  output bytes

A precondition for successful commissioning is a correctly installed device.
Check all the plug connectors (voltage, bus) and the pneumatic connections.
Set the bus addresses.

Instructions for this can be found in the chapters Installation and Configuration and Func-
tion of the Modules.

If there are RIO and/or intermediate modules in the system, these must be supplied with voltage and hence
switched on before or at least at the same time as the CANopen field bus module (FBM).

Here, using an example from the RS-Networx (Rockwell Automation), the configuration procedures are exp-
lained. Communication is done via the 1770-KFD Box.
For our example, the following structure has been chosen:

FreeLINE Type 8645, consisting of:
1 DeviceNet fieldbus module,
2 inside modules,
1 RIO 8640 and
 RIO 8645,
this system is to be placed into operation.
All modules are configured with 2-byte input and output data. The RIO 8640 is the exception, and is confi-
gured with 4 input and  outputs.

If RIO and/or inside modules are present in the system, these must be addressed first if the
desired module list is present in EEPROM.
Furthermore, all RIO and/or inside modules be supplied with current before the hub is sup-
plied with current. Otherwise, a correct actual module list cannot be created.