SYSTEM DESCRIPTION
Configuration errors in the station
Type No. Cause of error Resolution
3 1 The AirLine terminal is not cleared for
operation in the bus coupler.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
Remove the terminal from the station.
2 The length code of the AirLine terminal
corresponds to a length of 0 byte.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
Inspect the terminal and remove it from
your configuration if necessary.
3 The length code of the AirLine terminal
corresponds to a length of more than 32
bytes.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
Remove the terminal from the station.
4 The station contains a loop 1 module. Loop 1 modules are not cleared for
operation at the bus coupler.
Ascertain the precise location of the error
with the aid of the device-specific diagnosis
in your control.
Remove the module from the station and
replace it with a loop 2 module.
5 The sum of process data in the local bus is
greater than 250 bytes.
Check the number of process data and
reduce the number of terminals in the
station.
6 More than 64 AirLine terminals and loop 2
modules are plugged in.
Check whether more than 64 AirLine
terminals and loop 2 modules are present
in the station. If yes, reduce the number.
7 The sum of process data for the inputs and
outputs on the PROFIBUS is greater than
176 bytes.
(184 bytes in DPV0 mode)
Remove the terminals from the station.
8 More than eight PCP slaves are plugged
in.
Reduce the number of PCP terminals in
the station.