Owner's manual
82 - 8644/phoenix
SYSTEM DESCRIPTION
Error codes during DPV1 communication
If there is an error present during DPV1or PD-PCP communication in relation to an E/A module, this is
displayed via 0x44 on byte 2 of the data block.
DPV1 error:
Function_Num = 0xDE (Error Read) or 0xDF (Error Write)
Error_Decode = 0x80 (DPV1 communication)
Error codes during DPV1 communication
ATTENTION!
Error codes during DPV1 communication are errors in relation to DPV1/PCP. During DPV1
communication you will find the error code on byte 3, during communication in the process
data channel, error code 1 is located on byte 2 of the response. Pay attention to the individu-
al displays in your working environment at all times.
Error_Code_1 Error_Code_2 Comment
0xA0 0 Object from the field bus module cannot be read.
0xA1 0 Object from the field bus module cannot be written.
0xB0 0 Wrong index from the field bus module.
0xB1 0 The PB-PDU length is too small.
0xB2 0 wrong slot
0xB5 0 Module is busy.
0xB7 0 Error while writing on index 47 or 48.
0xD1 0 No PCP connection.
0xD2 0 Module has no PCP.
0xD3 0 Timeout from module.
0xD4 0 wrong service
0xD5 0 VC1 sequence not correct
0xD6 0 VC1 Length incorrect
0xF.. Error while writing module parameter.
0xF1 0 An incorrect module number was used.
0xF2 0 The parameter block is incomplete.
0xF3 0 The data length of the parameter block is too small.
0xF4 0 The data length of the parameter block is too big.
0xF5 0 The internal block for configuration, security value and
PCP is too small.
0xF6 0 Header byte from the module parameter block is not
correct.
0xF7 0 PCP initialisation for a module that has no PCP
functionality.
0xF8 0 Too many data blocks for the module.