In order to adapt the 16-channel digital modules to the data format of the control there is the opportunity to
switch the byte position for channel 1-8 and 9-16. By default, channels 9-16 (slot 3.x and 4.x) are on byte n
and channels 1-8 (slot 1.x and 2.x) are on byte n+1.
The format is switched with bit 4 in the control byte (parameter telegram, byte 11, see
Parameter telegram
section
). Channels 1-8 (slot 1.x and 2.x) are then on byte n and channels 9-16 (slot 3.x and 4.x) on byte
n+1.
Default (Bit 4=0)
Switched (Bit 4=1)
In order to adapt the 32-channel digital modules to the data format of the control there are opportunities to
switch the byte position of channel groups 1-8, 9-16, 17-24 and 25-32. By default, channel 1-8 (slot 1.x) are
on byte n+3 and channels 9-16 (slot 2.x) on byte n+2, channels 17-24 (slot 3.x) on byte n+1 and channels
25-32 (slot 4.x) on byte n.
If bit 6 is set in the control byte (parameter telegram, byte 11, see
Parameter telegram section
), switch the
format. Channels 1-8 (slot 1.x) are then on byte n and channels 9-16 (slot 2.x) on byte n+1, channels 17-24
(slot 3.x) on byte n+2 and channels 25-32 (plug 4.x) on byte n+3.
Default (Bit 6=0)
Switched (Bit 6=1)
Byte 0 1
Bit 7 6 54321 07 654321 0
Slot 4 3 2 1
Terminal point 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Byte 1 0
Bit 7654321 07 654321 0
Slot 4 3 2 1
Terminal point 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1 2.4 1.4 2.1 1.1
Switching round bytes in IB IL24 DI16 / IB IL24 DO16 terminals
Switching round bytes on IB IL24 DI32 / IB IL24 DO32 terminals
Byte 0 1 2 3
Bit 7 6 ... 1 0 7 6 ... 1 0 7 6 ... 1 0 7 6 ... 1 0
Slot 4 3 2 1
Terminal
point
8.4 7.4 ... 8.-
1
7.1 6.4 5.4 ... 6.1 5.1 4.4 3.4 ... 4.1 3.1 2.4 1.4 ... 2.1 1.1
Byte 0 1 2 3
Bit 7 6 ... 1 0 7 6 ... 1 0 7 6 ... 1 0 7 6 ... 1 0
Slot 1 2 3 4
Terminal
point
2.4 1.4 ... 2.1 1.1 4.4 3.4 ... 4.1 3.1 6.4 5.4 ... 6.1 5.1 8.4 7.4 ... 8.1 7.1