Instruction Manual
22
Technical Data
6.5.2. Electronic base module ME02, ME03 / 4-fold monostable
Technical Data ME02 / 4-fold
monostable
ME03 / 4-fold
monostable
Dimensions WxHxD 44 x 70.5 x 52 mm 66 x 93 x 60 mm
Weight 56 g 75 g
Storage temperature -20 ... +60° C -20 ... +60° C
Nominal load voltage DC 24 V DC 24 V
Number of valve outputs 4 4
Power consumption per valve location during
switching
43 mA 85 mA
Power consumption per valve location after
approx. 120 ms (for ME03 approx. 400 ms)
28 mA 52 mA
Power consumption from the backplane bus max. 10 mA max. 10 mA
Display of the valve status 1 yellow LED per valve
location
1 yellow LED per valve
location
Power loss of the module at the point of switching 4 W 8 W
Power loss of the module 120 ms after the switching
process (4 x 0.25 W power loss on resistors,
4 x 0.25 W on valve coils)
2 W -
Power loss of the module 400 ms after the switching
process (4 x 0.5 W power loss on resistors,
4 x 0.5 W on valve coils)
- 4 W
english
Type 8644