Instruction Manual

18
Technical Data
Ambient temperature
0 ... +55 °C 0 ... +55 °C 0 ... +55 °C
Operating voltage
24 V / DC, -15 % / +20 % tolerance**,
Residual ripple for field bus interface 5 %
* Power reduction (in the module)
** For the Ex-version maximum +10 %
*** The following restrictions apply to the power supply tolerances of the entire system (see Technical Data of the
entire system): Valve type: 0460 ± 10 %
Add-on dimension 16.5 mm
Operating principle
Valve
C/D (3/2-way)
Type 6526
L/N (5/3-way)
Type 0461***
Operating principle
Valve
H (5/2-way)
Type 6527
H (5/2-impulse)
Type 0461
Flow-rate
700 l/min 500 l/min
Pressure range
(with P shut-off)
2 ... 10 bar 2.5 ... 7 bar
Output
1 W 2 W 2 x 1 W
Current before
power reduction
42 mA 85 mA 41 mA
Current after
power reduction
33 mA 52 mA -
Valve locations (max.)
32 24
Electrical modules
2-fold, 3-fold*, 4-fold 2-fold bistable
Pneumatic modules
2-fold, 3-fold*, 4-fold 2-fold bistable
Ambient temperature
0 ... +55° C 0 ... +55° C
Operating voltage
24 V / DC, -15 % / +20 % tolerance**,
Residual ripple for field bus interface 5 %
* 3 x 10 mm valves for add-on dimension of 16.5
** For the Ex-version maximum +10 %
*** The following restrictions apply to the power supply tolerances of the entire system (see Technical Data of the
entire system): Valve type: 0461 ± 10 %
Interface (PROFIBUS)
PROFIBUS Copper line (RS-485), connected via PROFIBUS plug,
supply isolated, shielding connected galvanically to the functional earth
Recommended cable lengths see PROFIBUS system data
english
Type 8644