6.2 Adjustment menu 4 … 20 mA/HART
To damp process-dependent measured value fluctuations, you have to
set an integration time of 0 … 999 s in this menu item.
Depending on the sensor type, the factory setting is 0 s or 1 s.
In the menu item "Current output mode" you determine the output
characteristics and reaction of the current output in case of failure.
The default setting is output characteristics 4 … 20 mA, failure mode
< 3.6 mA.
In the menu item "Current output Min./Max.", you determine the
reaction of the current output during operation.
The default setting is min. current 3.8 mA and max. current 20.5 mA.