Manual

measured value indication and the current output. By activating the
appropriate curve, the volume percentage of the vessel is displayed
correctly. If the volume should not be displayed in percent but e.g. in l
or kg, a scaling can be also set in the menu item "Display".
Caution:
Note the following, if the respective sensor is used as part of an overll
protection system according to WHG:
If a linearisation curve is selected, the measuring signal is no longer
compulsorily linear proportional to the level. This must be taken into
consideration by the user, particularly when adjusting the switching
point on the level switch.
Entering a 4-digit PIN protects the sensor data against unauthorized
access and unintentional modication. In this menu item, the PIN is
displayed or edited and changed. However, this menu item is only
available if adjustment is enabled in the menu "Setup".
In delivery status, the PIN is "0000".
In this menu item, the internal clock of the sensor is adjusted.
The instrument settings are copied with this function. The following
functions are available:
l Store data from the sensor into the indicating/adjustment module.
l Store data from the indicating and adjustment module in the
sensor
The following data or settings for adjustment of the indicating and
adjustment module are saved:
Addition
al settings/PIN
Fur
ther settings/Date
time
Fur
ther settings/Copy
instrument settings
Indicating and adjustment module 25
6 Setup - sensors from software 4.0.0
41787-EN-120316