Manual

Th
e following values can be displayed:
l Height
l Pressure (only with pressure transmitters)
l Distance (only with radar, guided microwave, ultrasonics)
l Current
l Scaled
l Percent
l Lin. percent
l Temperature (only with pressure transmitters).
The selection "scaled" opens the menu items "Display unit" and
"Scaling". In "Display unit" there are the following options:
l Height
l Ground
l Flow
l Volume
l Without unit
Depending on selection, the dierent units are in turn available.
In the menu item "Scaling", the requested numerical value with
decimal point is entered for 0 % and 100 % of the measured value.
There is the following relationship between the indication value in the
menu "Display" and the adjustment unit in the menu "Device settings":
l With radar, guided microwave and ultrasonics, displayed value
"Distance" means: presentation of the measured value in the
selected adjustment unit, e.g. m(d)
l With pressure, displayed value "Pressure" or "Height" means:
presentation of the measured value in the selected adjustment
unit, e.g. bar or m.
Displayed value
Scaled
Display unit
Volume
l
Scaling
0 % = 0.0 l
100 % = 100.0 l
In the menu item "Current output" you determine the behaviour of the
current output during operation and in case of failure. The following
options are available:
Serv
ice/Current output
Indicating and adjustment module 19
5 Setup - Sensors up to software 3.99
41787-EN-120316