Echo curve
In this menu item you simulate a user-dened level or pressure value
via the current output. This allows you to test the signal path, e.g.
through connected indicating instruments or the input card of the
control system.
The following simulation variables are available:
l Percent
l Current
l Pressure (with pressure transmitters)
l Distance (with radar and guided microwave)
With Probus PA sensors, the selection of the simulated value is made
via the "Channel" in the menu " Basic adjustments".
How to start the simulation:
1 Push [OK]
2 Select the requested simulation variable with [->] and conrm with
[OK].
3 Set the requested numerical value with [+] and [->].
4 Push [OK]
The simulation is now running, with 4 20 mA/HART a current is
outputted and with Probus PA or Foundation Fieldbus a digital value.
How to interrupt the simulation:
à Push [ESC]
Information:
The simulation is terminated automatically 10 minutes after the last key
has been pushed.
Simulation
Start simulation?
With the reset function, modied values are reset. Three subfunctions
are available:
l Basic adjustment
- Reset the values modied with the indicating and adjustment
module to the sensor-specic basic setting
l Factory setting
Serv
ice/Simulation
Serv
ice/Reset
Indicating and adjustment module 15
5 Setup - Sensors up to software 3.99