Manual

32
Installation and wiring
Type 1062
+ -
A
+
-
200 mA max.
+
-
1
062
10-30 VDC
500 mA
+ -
A
200 mA max.
+
-
Power supply
Load 1
Reaction speed according
to the max. load
Green light (valve open
detection)
Orange light
(voltage present)
Load 2
Valve open
switch
Valve closed
switch
Red light (valve closed
detection)
Fig. 15: Wiring a version with two inductive 3-wire switches in
PNP mode, valve open and valve closed detection
8.2.5 Wiring a version with double
inductive 2-wire NAMUR switch
Respect the maximum allowable characteristics of the circuit
established with an inductive NAMUR switch shown in the table
below.
Max. authorised
ambient T°
Category
T° class
Ii [mA] (with
resistive limit)
Pi (mW)
U (V)
Ci (nF)
Li (µH)
100 °C II 2G T4 60 200 20 180 350
85 °C II 2G T5 60 200 20 180 350
80 °C II 2G T5 60 200 20 180 350
70 °C II 2G T6 60 200 20 180 350
english