Manual

note!
Caution risk of breakage!
• Do not use the coil as a lifting arm.
Body with welded sleeve: Use PVDF.
Body with bonded sleeves: Use Tangit special adhesive.
Valve body must not be installed under tension.
Observe direction of flow:
The arrow on the body indicates the direction of flow (no function
in opposite flow direction).
6.4. Manual emergency actuation
Caution!
Discharge of medium due to loss of the O-rings!
If the O-rings are lost, the valve will leak. Medium may be
discharged.
note!
Caution!
• When the manual emergency actuation is locked, the valve can no
longer be actuated electrically.
Manual emergency
actuation
Press
Turn
1
2
english
6.5. Electrical connection of the cable plug
Warning!
Risk of injury due to electrical shock!
Before reaching into the device / equipment switch off the power
supply and secure to prevent reactivation!
Observe applicable accident prevention and safety regulations for
electrical equipment!
If the protective conductor contact between the coil and body is
missing, there is danger of electrical shock!
Always connect protective conductor.
Check electrical continuity between coil and body.
Authorized cable plug e.g.
Type 2508 or other suitable
cable plug in accordance with
DIN EN 175301-803 Form A
Seal
max. 1 Nm
Note the voltage and current type as specified on the type
label.
Procedure:
Tighten cable plug (for permitted types see data sheet), observing
max. torque 1 Nm.
Check that seal is fitted correctly.
Connect protective conductor and check electrical continuity
between coil and body.
6.5.1. Electrical connection - Pulse
DC connections:
Terminal 1 = closed +
Terminal 2 = open +
Terminal 3 = GND -
Protective conductor
connection
24 3
1
english
The connection terminals in the cable plug are identified with
the numbers 1 to 3 according to the terminals on the valve.
Procedure:
Connect the pulse valves (variable code CF 02).
For direct current versions connect negative terminal to terminal 3.
note!
Important information:
Avoid emitting pulses simultaneously to both coil windings.
Do not switch any other consumers (relays, etc.) at the same time
as the terminals.
The coil connection, to which voltage is not applied, must be gal-
vanically isolated (open).
If two or more valves are switched in parallel, ensure that this
requirement is met by using 2-pole or multi-pole switches.
7. MAINTENANCE, TROUBLESHOOTING
7.1. Safety instructions
Warning!
Risk of injury from improper maintenance!
Maintenance may be carried out by authorized technicians only
and with the appropriate tools!
Risk of injury from unintentional activation of the system and
an uncontrolled restart!
Secure system from unintentional activation.
Following maintenance, ensure a controlled restart.
7.2. Malfunctions
If malfunctions occur, check:
the device has been installed according to the instructions,
the electrical and fluid connections are correct,
the device is not damaged,
all screws have been tightened,
the voltage and pressure have been switched on,
the pipelines are clean.
english