Specifications

Commands
Set up your command (output) channels from the Commands tab.
MMooddee..
Use the drop-down menu in the Mode field to select
whether the output type is Momentary or Latching.
Momentary is for command signals that last for as long as
the specified duration setting. Select Latching if the
command signal stays active until changed by another
command. Latching command outputs ignore any duration
setting.
Note: If you change the mode from latching to momentary
while the latching command is active, the channel will remain
latched until a new command is issued on that channel.
Note: When you set a channel for latching, both the A and B
output for that channel must be configured as latching since
the two work in conjunction with each other. Similarly, if your
output is configured for momentary, both the A and B state
must be set for momentary even though the A and B states
work independently.
DDuurraattiioonn..
In the Duration field, specify the amount of time the command output is to be active – anywhere from
0.1 to 25.5 seconds, definable in 1/10-second increments. Command channels A and B are mutually exclusive
(when channel B is active, channel A is inactive, and vice-versa).
AA LLaabbeell // BB LLaabbeell..
A and B labels correspond to A and B output channels on the Command Relay. Specify a label
to identify both command actions. These labels are displayed in the command buttons in the Lynx monitor view,
as well as in the drop-down menus you use during alarm/action setup. If you are using a Voice Interface,
command labels will also be announced during a voice session.
Timed Events
Use the Timed Events tab to schedule activities at your site.
The GSC3000 and VRC2500 can perform data captures,
commands and macros on the schedule you determine here.
Events saved to one I/O can involve actions on any I/O unit
at the same site.
TTiimmee..
Click the Time field, followed by the drop-down arrow
that appears, for a pop-up dialog allowing you to set the
schedule for this action.
In the Date area, choose whether the event will occur Every
Day, on one Specific Weekday, or on one Specific Day of the
Month, and choose the day within the week or month as
appropriate. For the Month field, indicate whether this event
will occur Every Month or during one Specific Month. In the
Time area, select whether this event will occur Every Hour,
Every Minute, or Every Second on the specified day(s), or
designate the Specific Time for the event to take place.
CHAPTER 4: I/O UNIT CONFIGURATION
39
CUSTOMER SUPPORT: 978-486-3711 • support@burk.com • www.burk.com