Specifications
UUnniitt..
Enter the unit of measurement (i.e. volts, watts, amps, etc.) used by this metering channel (up to four
characters). The Voice Interface is able to recognize the following abbreviations and speak the full unit name:
%%
Percent
AAMMPPSS
Amps
DDBB
Decibels
DDEEGG
Degrees
GGAALL
Gallons
KKVV
Kilovolts
KKWW
Kilowatts
LLBBSS
Pounds
MMAA
Milliamps
MMIINN
Minutes
MMVV
Millivolts
PPOOWWRR
Power
SSEECC
Seconds
VVLLTTSS
Volts
WWAATTTT
Watts
TTyyppee..
Click in the Type field and use the drop down menu to select the type of metering this channel uses:
After you set up names, units and input types for your
channels, click the + sign to the left of the channel
number to set up limits and alarms, and to associate
events with those channel alarms.
LLiimmiittss..
You can set up four separate limit parameters for each channel (two lower limits and two upper limits),
allowing different alarms to be issued and actions to be taken depending on which limit has been exceeded.
Enter the limits in ascending order, according to the metering value:
SSeeccoonndd LLoowweerr
The lowest limit value. Any meter reading at or below this value will cause the
alarm/action associated with the Second Lower limit.
FFiirrsstt LLoowweerr
The higher of the two lower limits. When the monitored value reaches the First
Lower limit, the associated alarm/action is initiated until the value reaches the
Second Lower limit. If only one lower limit is needed, use the second lower limit, as
the system responds only to the second limit when both are exceeded. Leave the
first lower limit set to 0.
GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL
CHAPTER 4: I/O UNIT CONFIGURATION
36
00 ttoo 1100
Allows an analog input of 0VDC up to +10VDC with the same ratio assigned for all
values in that range.
--55 ttoo ++55
Allows an analog input of –5VDC to +5VDC with the same ratio assigned for all
values in that range.
LLiinneeaarr ttoo PPoowweerr
Allows an analog input to this channel of 0VDC up to +10VDC with an exponential
ratio calculated for all values in that range.
IInnddiirreecctt PPoowweerr
Disables direct input to the channel. The displayed value is based on the input
values of the previous two channels. For example, the value of Channel 2 and the
value of Channel 3 are multiplied to give the value for Channel 4.