User Manual

www.bullard.com
Pre-Operational Inspection
Before each entry into a contaminated area, the following inspection must be
performed to ensure proper function of the respirator system. If damage is
found on any component, do not use.
1. PAPR System
Closely inspect the entire EVA Powered Air-Purifying Respirator (PAPR)
system including the filter / cartridge, battery, hood and breathing
tube. Pay attention to component connection points for wear and
damage. If parts are missing or damaged, replace them with only
Bullard branded/manufactured replacement parts before proceeding.
2. Filter / Cartridge
Inspect the filter / cartridge for physical damage.
Check the label to ensure the filter / cartridge has not exceeded its
“use-by” date.
• Inspect the gasket on the filter for physical damage.
Ensure that the correct filter / cartridge is appropriate for the
contaminated area.
3. Battery
Inspect the battery for any physical damage.
Check the Fuel Gauge to determine sufficient charge is available.
The battery must be latched to the turbo-blower. The battery tab will
click when completely engaged.
4. Hood
Inspect the hood for any physical damage.
5. Breathing Tube
Ensure that a rubber gasket is installed into the air source connection
on the turbo-blower unit.
Examine the breathing tube for tears, holes, or cracks.
The breathing tube should screw securely into the air source
connection and the hood.
6. Airflow Check
The EVA Powered Air-Purifying Respirator (PAPR) system is pre-
calibrated to ensure required airflow. However, the Airflow Indicator
must be used to verify minimum required airflow is attained prior to
each day’s use. The airflow should be checked with your current filter /
cartridge installed.
See Checking Airflow with Airflow Indicator under Operational
Instructions for correct operation of the airflow check.
7. Check Low Flow Alarm
See Checking Low Flow Alarm under Operational Instructions to verify
Low Flow Alarm is functioning properly.
Setup and Getting Started
Important:
Perform a Pre-Operational Inspection prior to use. See section Pre-
Operational Inspection.
1. Battery Charging and Installation
Battery charging
a. Connect the battery charger to a
220-230V electrical outlet (110-
120V if applicable).
b. Place the battery upside down
into the charging port of the
battery charger.
c. Charge the battery for
approximately four (4) hours.
While the battery is charging,
the light on the charger will
remain red. The charger light will
illuminate green when charging
is complete.
Battery Installation
a. Insert the battery into the battery compartment on the turbo-blower unit.
The battery tab will click when completely engaged.
b. To remove the battery from the turbo-blower unit, press the battery
release tab on the battery and pull the battery up and out.
4
1 2