Installation guide

A-8
Installation Guide
NovaScale 5325 Server Specifications
NovaScale 5325 Servers are delivered rack-mounted in 40U cabinets.
The following web site may be consulted for general site preparation information:
http://www.cs.bull.net/aise.
Cabinet Dimensions / Weight
Unpacked Packed
1300H
Height: 195.5 cm (77.0 in)
Width: 60.0 cm (23.6 in)
Depth: 129.5 cm (51.0 in)
Weight (max): 670 kg (1427 lb)
1300H
Height: 200.0 cm (78.7 in)
Width: 80.0 cm (31.5 in)
Depth: 140.0 cm (55.1 in)
Weight (max): 700 kg (1491 lb)
Service Clearance
Front
Rear
Side (free side)
150 cm
100 cm
100 cm
Operating Limits
Dry bulb temperature range
Relative humidity (non-condensing)
Max. wet bulb temperature
Moisture content
Pressure / Elevation
+15°C to +30°C (+59°F to +86°F)
Gradient 5°C/h (41°F/h)
35 to 60% (Gradient 5%/h)
+24°C (+75.2°F)
0.019 kg water/kg dry air
Sea level < 2500 m
Optimum Operational Reliability
Temperature
Hygrometry
+ 22°C (+ 3°C) (+ 72°F (+ 5°F)
50% (+
5%)
Non-Operating Limits
Dry bulb temperature range
Relative humidity (non-condensing)
Max. wet bulb temperature
Moisture content
+5°C to +50°C (+41°F to +122°F)
Gradient 25°C/h (77°F/h)
5 to 95% (Gradient 30%)
+28°C (+82.4°F)
0.024 kg water/kg dry air
Shipping Limits
Dry bulb temperature range
Relative humidity (non-condensing)
-35°C to +65°C (-31°F to +149°F)
Gradient 25°C/h (77°F/h)
5 to 95% Gradient 30%/h
Acoustic Power at Room Temperature +20° C (+68° F)
System Running System Idle
Lw(A) 6.3 Bels Lw(A) 6.1 Bels