Installation guide

2-10
Installation Guide
PDU Power Cable Socket
1. Check that the power supply cable is not live with the multimeter.
2. Carefully guide the PDU power supply cable (cable with extra 1.5 meter length) through
the left–hand cable inlet at the base of the cabinet.
3. Check that the power supply cable is long enough for connection to the PDU.
4. Remove the power socket from the PDU plug.
5. Unscrew the base of the socket (A), insert the cable through the socket base (B), and
wire to the socket head, as shown in Figure 46.
6. Screw the socket base back to the socket head (C).
7. Check for <
0.1 ohm resistance between the grounding pin on the power cable plug and
the metal frame with the multimeter.
8. Connect the power supply cable socket to the PDU power cable plug.
9. Use velcro fasteners to secure the cable into place along the cabinet frame.
10.Check that the power switches on the peripheral devices are set to ON:
Peripheral Device
Power Switch Location
KVM Switch 1 switch – rear left
Disk Rack 2 switches – rear right and left
PAP Unit 1 switch – front right
Monitor 1 switch – right side
CSS Module Power Cable Socket
1. Check that the power supply cable is not live with the multimeter.
2. Firmly pull on the power socket lever to remove from the CSS module plug.
3. Remove the power socket from the CSS module plug.
4. Unscrew the base of the socket (A), insert the cable through the socket base (B), and
wire to the socket head, as shown in Figure 46.
5. Screw the socket base back to the socket head (C).
6. Check for < 0.1 ohm resistance between the grounding pin on the power cable plug and
the metal frame with the multimeter.
7. Connect the power supply cable socket to the CSS module power cable plug.
8. Use velcro fasteners to secure the cable into place at the base of the cabinet.
9. Carefully place the power supply cable plug/socket assembly in the plenum space at the
base of the cabinet.