Installation guide

1-12
Installation Guide
Important:
The front door opens flush with the front of the cabinet (180_ opening angle) and may
be fitted on either side of the cabinet frame, according to site requirements. Full
access to the cabinet is mandatory for maintenance.
Customers are advised to plan ahead and to provide space for extensions.
2. Take care to leave sufficient access to raised floor cable cut–outs.
35 cm
(14 in)
<
>
15 cm
(6 in)
<
<
Cable cut–out
><
<
<
Main Cabinet
113 cm
(44.5 in)
65 cm
(25.6 in)
FRONT
REAR
35 cm
(14 in)
<
>
15 cm
(6 in)
<
<
Cable cut–out
><
I/O Cabinet
65 cm
(25.6 in)
Figure 14. Cabinet cable cut–outs
3. Lower the four jacking screws with the 27 mm hex wrench and lock firmly into place to
secure the cabinet.
Figure 15. Locking jacking screws
4. Check cabinet stability and horizontality.
DANGER
The CSS module inside the cabinet is extremely heavy. It is mandatory for cabinet
jacking screws to be locked safely into place before use or maintenance. Incorrect
installation may result in serious personal injury or damage to components.