Specifications

A-19
Specifications and Features
Power Cables
PDU-0-7-M-32A
AC (32A)
Cable type
Connector type
1 per PDU
3 x AWG10 ( 3 x 6 mm
2
/ #10US)
IEC60309-32A
CSS Module
AC (20A)
Cable type
Connector type
1 per CSS Module
3 x AWG12 (3 x 4mm
2
/ #12US)
IEC60309-32A
It is mandatory for power lines and terminal boxes to be located within the immediate vici-
nity of the system and to be easily accessible. Each power line must be connected to a se-
parate, independent electrical panel and bipolar circuit breaker.
PDUs require an extra cable length of 1.5 meters for connection inside the cabinet.
Electrical Specifications
(power supplies are auto-sensing and auto-ranging)
Current draw
Power consumption
Thermal dissipation
29.5 A max. at 200 VAC input
3000 VA per full CSS module)
1500 VA (per PDU)
2700 W / 9250 BTU (per full CSS module)
1300 W / 4610 BTU (per PDU)
Europe
Nominal voltage
Voltage range
Frequency
230 VAC (Phase / Neutral)
207 - 244 VAC
50 Hz 1%
United States of America
Nominal voltage
Voltage range
Frequency
208 VAC (Phase / Neutral)
182 - 229 VAC
60 Hz 0.3%
Japan
Nominal voltage
Voltage range
Frequency
200 VAC (Phase / Neutral)
188 - 212 VAC
60 Hz 0.2%
Brazil
Nominal voltage
Voltage range
Frequency
220 VAC (Phase / Neutral)
212 - 231 VAC
60 Hz 2%
Breaker Protection
Mains power CSS module
Maximum inrush current
Mains power PDU
20A Curve C
210A / per quarter period
20A Curve C
Maximum inrush current
Mains power PDU
Maximum inrush current
210A / per quarter period
20A Curve C
210A / per quarter period
Table 15. NovaScale 5320/6320 Server specifications