Site Preparation Guide REFERENCE 86 A1 87EF 08 NOVASCALE NovaScale Servers
BLANK
NOVASCALE NovaScale Servers Site Preparation Guide Hardware December 2006 BULL CEDOC 357 AVENUE PATTON B.P.
The following copyright notice protects this book under Copyright laws which prohibit such actions as, but not limited to, copying, distributing, modifying, and making derivative works. Copyright Bull SAS 1992, 2006 Printed in France Suggestions and criticisms concerning the form, content, and presentation of this book are invited. A form is provided at the end of this book for this purpose.
Preface Table of Contents Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Intended Readers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Definition of Safety Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . General Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2. Fitting out the Premises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Data Processing Center Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Planning Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable Cut-outs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grounding the Raised Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Neutral Power System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Constructing a TN-S Neutral Point Connection System . . . . . . . . . . . . . . . . . . . . . . . Non-Computing Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Prerequisites . . . . . . . . . . . . . . . . . . . . .
vi Site Preparation Guide
List of Figures Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure Figure 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. Bull server cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Required unpacking area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Recommended Data Processing Center layout . . . . . . . . .
List of Tables Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table Table viii 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. NovaScale Blade 20xx cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NovaScale Blade 20xx Chassis specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NovaScale Blade 2020 Server specifications . . . . . . . .
Intended Readers This Site Preparation Guide explains how to prepare a Data Processing Center for Bull servers, in compliance with the standards in force. It is to be used by all personnel and trade representatives involved in the site preparation process. • General Recommendations describes delivery requirements • Chapter 2. Fitting out the Premises describes general site layout and requirements. • Chapter 3. Air-Conditioning describes site air-conditioning requirements. • Chapter 4.
General Recommendations It is mandatory to comply with the procedures, design requirements and recommendations set out in this guide. The construction of the Data Processing Center and the installation of ancillary facilities must comply with: • the level of safety required by the standards and laws in force in the country where the server is to be installed, • the Customer's requirements in terms of continuity of service.
Regulatory Specifications and Disclaimers Declaration of the Manufacturer or Importer We hereby certify that this product is in compliance with European Union EMC Directive 89/336/EEC, using standards EN55022 (Class A) and EN55024 and Low Voltage Directive 73/23/EEC, using standard EN60950. The product has been marked with the CE Mark to illustrate its compliance.
Federal Communications Commission (FCC) Statement Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Environmental Standards Climatic and Atmospheric Specifications The servers comply with standards: • IEC 60068.2.1 IEC 60068.2.2 IEC 60068.2.
Protection against Electrostatic Discharges CMOS (Complementary Metal Oxide Semiconductor) technology is highly sensitive to electrostatic discharges. The use of conductive antistatic flooring is strongly recommended. Maintenance personnel must wear wrist-straps before handling electronic equipment. A ground socket is provided in each cabinet.
Pollution Limits The servers comply with standard: • NFX44-101, Class 4 000 000 Audio-Noise Limits The servers comply with standards: • ISO 7779 • ISO 11201 • ISO 7574 • ISO 4871 • ISO 9295 • ISO 9296 • IEC 61260 • IEC 60651 (Bull NovaScale 5xx5 Series & Bull NovaScale 5xx5 Series) • IEC 61672-1 (Bull NovaScale 4000 Series) • IEC 61672-2 (Bull NovaScale 4000 Series) Operating LwAd Acoustical Power • 7.
xvi Site Preparation Guide
Chapter 1. General Requirements This chapter explains delivery and unpacking requirements for the servers. It includes the following topics: • Server Cabinet, on page 1-1 • Delivery Conditions, on page 1-2 • Carry-In Route, on page 1-2 • Unpacking Requirements, on page 1-3 Server Cabinets The servers are delivered rack-mounted and pre-cabled in one or two 19U / 40U cabinets, according to the version chosen. Figure 1.
Delivery Conditions The server is delivered 24 hours in advance of the scheduled installation date. On arrival, the server must be placed, in its packing, in the Computer Room so that it reaches room temperature before powering up (optimum operating temperature = 22° C + 3° C, hygrometry = 50% + 5%). Warning: To avoid incorrect handling, the server must be removed from its packing by authorized Customer Service Engineers only.
Unpacking Requirements The cabinet is delivered packed on a pallet with rails for easy unloading. The Data Processing Site manager must set aside the required working area for unpacking, as shown in the following figure. See Appendix A. Specifications for packing size. Figure 2. Required unpacking area Important: Cabinet depth varies according to server model (130 / 110 cm). See Appendix A. Specifications for details.
1-4 Site Preparation Guide
Chapter 2. Fitting out the Premises This chapter explains how to plan and fit out your premises to receive your server.
ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ ÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇÇ For optimum site safety and security, the following figure shows an example of recommended Data Processing Center layout.
Planning Installation Installation must be planned so that any changes and / or extensions may be implemented with minimum service disruption. Use the layout grid shown in Figure 7 to plan installation. Each square of the grid represents a standard raised floor panel. CAUTION: It is mandatory for Data Processing Center layout to take the safety of personnel into account. Access for stretchers must be provided around the server and peripherals.
Network Cables The following table indicates the number of Ethernet and Modem cables to be routed to the cable cut-out at the base of each cabinet if the server is to be connected to the Customer's LAN (for remote operation, administration, or maintenance): Server Network Cable Production: 1 to 4 x 10/100/1000 Mb Ethernet cable per NovaScale Blade 2xxx embedded Ethernet Switch. Management: 1 x 10/100 Mb Ethernet cable per Servers Chassis Management Module.
Service Clearance It is mandatory to comply with the service clearance requirements indicated in the following figures: Rear door 100 cm (39.4 in) Server Cabinet Depth * Server/ Wall 100 cm (39.4 in) Width * Server/ Wall 100 cm (39.4 in) 150 cm (59 in) Figure 5. Single cabinet service clearance Rear doors 100 cm (39.4 in) Main Cabinet Depth * Server/ Wall 100 cm (39.4 in) Width * Extension Cabinet Width * Server/ Wall 100 cm (39.4 in) 150 cm (59 in) Figure 6.
1 square = 60 x 60 cm Figure 7.
Electrical / Electromagnetic Interference Generators of electromagnetic interference may adversely affect server operation. The following sources of electrical and / or electromagnetic interference must not be located in the immediate vicinity of the Data Processing Center: • high-voltage lines, • radars, • radios or other transmitters. The server must not be subjected to electric / magnetic fields in excess of: • electric field (E): 3 V/m, • magnetic field (H): 30 A/m.
Extinguishing Agents In compliance with APSAD R13. Commonly used extinguishing agents are: • inert gases such as ARGONITE (Argon-based) and INERGEN, • water in the form of sprinklers or sprays (pending certification). CAUTION: It is strongly recommended not to use CO gas (hazard to personnel and to equipment). The use of HALON 1301 gas is prohibited as from January 1 2003.
Computer Room Floor Primary Floor The primary floor must be sloped and equipped with a drain. Primary floor resistance must be > 600 daN/m . The primary floor and wall risers located at raised floor level must be coated with dustproof paint. Raised Floor CAUTION: A raised floor compliant with Standard NF P67 103-1 and 103-2, dated April 1993 is mandatory for the Bull NovaScale Servers.
Actuators alone Figure 9. Actuators and T–beam section spars Raised floor structure CAUTION: If the air-conditioning unit(s) is (are) placed on brackets in the room, it is mandatory to electrically isolate these brackets from the raised floor slabs, crossbeams, and actuators. Computer Room Ceiling It is extremely important to have sufficient ceiling height so that the premises may be airconditioned without creating draughts. Optionally, a suspended ceiling may be installed.
Sound-Proofing The sound level in the Computer Room may be relatively high due to room structure, air-conditioning and hardware ventilation systems. The most effective means of attenuating noise are to: • use dedicated rooms (Printing Room, Console Room, etc.), • install a suspended ceiling, • sound-proof walls and partitions. Protection from Sunlight Large glass surfaces must be protected from sunlight. In no event may the Bull NovaScale Server be exposed to direct sunlight.
Media Storage Room Media may be stored in the Computer Room or in an adjacent room, in which case Computer Room environmental conditions are applicable. The Media Storage Room floor must be designed to support loads of up to 10 kN/m . Media is sensitive to high-power electromagnetic fields. Media must not be stored in the vicinity of electric ducts, lightning rod chutes, transformers, etc. Paper Storage Room The Paper Storage Room floor must be designed to support loads of up to 10 kN/m .
Chapter 3. Air-Conditioning This chapter explains air-conditioning requirements for the servers. It includes the following topics: • Air-Conditioning System Features and Functions, on page 3-1 • Air-Conditioning System Specifications, on page 3-2 • Checks and Alarms, see page 3-5 CAUTION: An air-conditioning system, compliant with the requirements of NF X44-101, Class 4 000 000, dated June 1981 and with ISO 7730, is mandatory for the Bull NovaScale Server.
Air-Conditioning System Specifications Warning: If the air-conditioning system is shut down, "operational" conditions must be re-established, in compliance with temperature and hygrometry gradients, AT LEAST ONE HOUR before powering up the server. To optimize the air duct network, air-conditioning cabinet(s) must be installed in the Computer Room or in an adjacent room. Filters must be easily accessible for regular checks and easy cleaning.
Circulation The servers are cooled by taking air from inside the room. The following requirements are to be complied with for correct air circulation of air: • raised floor height: > 30 cm, • the raised floor plenum must not be obstructed by oversize pipes or cableways, • raised floor slabs must be correctly fitted. Warning: Do not place perforated / damper slabs in the immediate vicinity of one or more air-conditioning cabinets, as shown in the following figure.
Pollutants There are three types of pollutants: • liquids, • solid particles, • gases. Damage varies according to pollutant type and interaction: corrosion, erosion, mildew, oxidation, etc. Solid particles are abrasive, electrostatic, and absorbent. They generally originate from: • surface crumbling of construction materials used to fit out the Data Processing Center, • the formation of rust inside air conditioning units and on raised floor supports, • systems (e.g. printers, ...
Checks and Alarms The air-conditioning system is controlled automatically. Variations outside the specified temperature and hygrometry ranges must be transmitted to Customer Service Engineers. Detectors must be installed at the air-conditioning cabinet air inlet and / or in the Computer Room. Alarms must indicate any variation outside the specified Computer Room climatic environment conditions.
3-6 Site Preparation Guide
Chapter 4. Power Supply This chapter explains power supply requirements for Bull NovaScale Servers. It includes the following topics: • Power Supply, on page 4-1 • Cabling Requirements, on page 4-2 • Grounding Circuit, on page 4-5 • Neutral Power System, on page 4-6 • Non-Computing Power Supply, on page 4-8 DANGER A power supply compliant with Standard NFC 15.100, dated May 1991, is mandatory for the servers.
DANGER • To ensure the protection of personnel and equipment, bipolar magneto-thermic circuit breakers must be installed on the phase and neutral wires, in compliance with the safety standards in force. • Power must be exclusively conveyed by copper conductors from the source. Aluminium conductors are prohibited. It is mandatory to separate the power supply for the server from the non-computing power supply.
Mounting Power Supply Cable Sockets CAUTION: To be performed by a certified electrician only. Tools Required • Multimeter • Phillips screwdriver • Velcro fasteners Europe, Brazil PDU/UPS power cables are equipped with ready-mounted IEC60309 plugs. The Customer is responsible for supplying and installing appropriate sockets for connection to the site power supply. Except for UPS 7.5 & 10 KVA: Power Cables are hard wired directly in the UPS without plug. Figure 12.
For PDU/UPS equipped with IEC 60309 plugs. 1. Check that the power supply cable is not live with the multimeter. 2. Carefully guide the power supply cable through the cable inlet at the base of the cabinet. 3. Check that the power supply cable is long enough. 4. Unscrew the base of the socket (A), insert the cable through the socket base (B), and wire to the socket head, as shown in Figure 14. Figure 14. PDU/UPS Power socket 5. Screw the socket base back to the socket head (C). 6. Check for < 0.
Grounding Circuit The electronic components inside the servers are sensitive to high-frequency electromagnetic interference. To ensure correct hardware operation, high-frequency interference must be limited via an equipotential ground circuit and metallic braid shielded cables. DANGER For the protection of personnel and hardware, it is mandatory for the grounding network to be compliant with Data Processing Center requirements and the standards in force.
Figure 15. Raised floor equipotentiality method Neutral Power System A TN-S neutral point connection system is mandatory for the servers. Constructing a TN-S Neutral Point Connection System The servers are equipped with a high-leakage current switch-mode power supply. The protective conductor (PE) is connected to the neutral conductor at the origin of the installation.
Power Supply Interface N N Electricity Distribution Panel P.E Data processing equipotential line = flexible multi-strand wire in compliance with standard NFC 15.100. Data processing equipotential bar Raised floor actuator meshing braid Computer and peripherals cab. cab. P.E Y/G Main earth plate terminal Measurement bar Figure 16.
Non-Computing Power Supply Prerequisites • Installation of current outlets around the edge of the computing room. • The non-computing power supply (air-conditioners, lighting, etc.) must be separated from the data processing power supply by specific distribution cabinets. Note: The Customer is responsible for supplying the complete electrical installation, from the power delivery station through to the cable outlets at the base of the server cabinet.
Appendix A.
NovaScale Blade 2xxx Cabinet Specifications NovaScale Blade chassis are delivered rack-mounted in a 19U or 40U cabinet. Cabinet Dimensions / Weight Unpacked Packed 1100H Height: Width: Depth: Weight (empty): Weight (max): 1100H 195.5 cm (77.0 in) 60.0 cm (23.6 in) 111.5 cm (43.9 in) 205 kg (452 lbs) 600 kg (1330 lbs) 1100L Height: Width: Depth: Weight (empty): Weight (max): Height: Width: Depth: Weight (empty): Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 122.0 cm (48.
Electrical Specifications (power supplies are auto-sensing and auto-ranging) Power consumption 5000 VA (max. per chassis) Thermal dissipation 4706 W / 16067 BTU (max.
NovaScale Blade 20xx Chassis Specifications Dimensions / Weight Height 30.42 cm (23.25 in, 7U) Width 44.4 cm (17.5 in) Depth 71.1 cm (28.0 in) Weight Chassis + modules + Blades: 108.86 kg (240 lbs) maximum Chassis + modules: 44.
NovaScale Blade 2020 Server Specifications Dimensions / Weight Height Width Depth Maximum Weight 24.5 cm (9.7 in) 2.9 cm (1.14 in) 44.6 cm (17.6 in) 5.4 kg (12 lbs) Electrical Power Voltage range (VDC) Table 3. Redundant 12 VDC (220 W max.) 12 VDC NovaScale Blade 2020 Server specifications NovaScale Blade 2021 Server Specifications Dimensions / Weight Height Width Depth Maximum Weight 24.5 cm (9.7 in) 2.9 cm (1.14 in) 44.6 cm (17.6 in) 5.4 kg (12 lbs) Electrical Power Voltage range (VDC) Table 4.
NovaScale Blade 2320 Server Specifications Dimensions / Weight Height Width Depth Maximum Weight 24.5 cm (9.7 in) 2.9 cm (1.14 in) 44.6 cm (17.6 in) 5.4 kg (12 lbs) Electrical Power Voltage range (VDC) Table 6. A-6 Dual redundant 12 VDC (400 W max.
NovaScale 3005 Series Server Cabinet Specifications The Novascale 3005 Series are delivered rack-mounted in a 19U or 40U cabinet. 40U Cabinet Dimensions / Weight Height: Width: Depth: Weight (empty): Weight (full): Unpacked 195.0 cm (77.0 in) 65.0 cm (25.6 in) 113.6 cm (44.7 in) 225 kg (496 lb) 680 kg (1280 lb) Height: Width: Depth: Weight (empty): Weight (full): Packed 200.5 (80.7 in) 80.0 cm (31.5 in) 120.0 cm (47.
Electrical specifications (power supplies are auto-sensing and auto-ranging) Current draw 24 A max. at 240 VAC input per PDU Power consumption 8800 VA (max. 40U cabinet) 5500 VA (max. 19U cabinet) 5700 VA (max. per PDU) Thermal dissipation 1500 VA / 5100 BTU (per Novascale 3045 CPU drawer) Nominal voltage Voltage range Frequency Nominal voltage Voltage range Frequency Nominal voltage Voltage range Frequency Nominal voltage Voltage range Frequency Mains power PDU Maximum inrush current Table 7.
Novascale 3025 Server CPU Drawer Specifications Height: Width: Depth: Weight (base model) Weight (max) Power Voltage range (VAC) Frequency Current Thermal output (typical) Dimensions/Weight 17.6 cm (6.9 inches, 4U) 44.1 cm (17.3 inches) 76.5 cm (30.1 inches) 21 kg (46.3 lbs) 48 kg (105.8 lbs) Electrical 1760VA 200 VAC to 240 nominal, autoranging (+6% -10%) 50 to 60 Hz ± 5% 6.
NovaScale 3045 Server CPU Drawer Specifications Height: Width: Depth: Weight (base model) Weight (max) Power Voltage range (VAC) Frequency Current Thermal output (typical) Dimensions/Weight 17.6 cm (6.9 inches, 4U) 44.1 cm (17.3 inches) 76.5 cm (30.1 inches) 21 kg (46.3 lbs) 48 kg (105.8 lbs) Electrical 1760VA 200 VAC to 240 nominal, autoranging (+6% -10%) 50 to 60 Hz ± 5% 6.
NovaScale 3045 COMPACT Server CPU Drawer Specifications Height: Width: Depth: Weight (base model) Weight (max) Power Voltage range (VAC) Frequency Current Thermal output (typical) Dimensions/Weight 8.7 cm (3.4 inches, 2U) 44.1 cm (17.3 inches) 76.5 cm (30.1 inches) 21 kg (46.3 lbs) 33 kg (72.8 lbs) Electrical 1280VA 200 VAC to 240 nominal, autoranging (+6% -10%) 50 to 60 Hz ± 5% 6.
NovaScale 4020/4040 Server Cabinet Specifications NovaScale 4020 / 4040 servers are delivered rack-mounted in a 40U or 19U cabinet. Cabinet Dimensions / Weight Unpacked Packed 1100H Height: Width: Depth: Weight (empty): Weight (max): 1100H 195.5 cm (77.0 in) 60.0 cm (23.6 in) 111.5 cm (43.9 in) 135 kg (298 lb) 935 kg (2062 lb) 1100L Height: Width: Depth: Weight (empty): Weight (max): Height: Width: Depth: Weight (empty): Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 122.0 cm (48.
Electrical Specifications (power supplies are auto-sensing and auto-ranging) Power consumption Thermal dissipation 8800 VA (max. 40U cabinet) 5500 VA (max. 19 U cabinet) 5700 VA (max. per PDU-20A) 7300 VA (max.
NovaScale 4020 Server CPU Drawer Specifications Dimensions / Weight Height Width Depth Weight 8.77 cm (3.5 in, 2U) 44.9 cm (17.7 in) 74.7 cm (29.
NovaScale 4040 Server CPU Drawer Specifications Dimensions / Weight Height Width Depth Weight 17.53 44.45 71.12 48.08 cm (6.9 in, 4U) cm (17.5 in) cm (28.0 in) kg (106 lb) Electrical Power Voltage range (VAC) Frequency Current Thermal output (typical) 1500 VA 200 VAC to 240 VAC nominal, autoranging +6%, -10% 50 to 60 Hz 5% 6.
NovaScale 5080/5160/6080/6160 Specifications NovaScale 5080/5160 Servers are delivered rack-mounted in 40U cabinets. Cabinet Dimensions / Weight Unpacked Packed 1300H 1300H Height: Width: Depth: Weight (max.): 195.5 cm (77.0 in) 60.0 cm (23.6 in) 129.5 cm (51.0 in) 943 kg (2079 lb) Height: Width: Depth: Weight (max.): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 140.0 cm (55.
Power Cables PDU-0-7-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 ( 3 x 6 mm2 / #10US) IEC60309-32A CSS Module AC (20A) Cable type Connector type 1 per CSS Module 3 x AWG12 (3 x 4mm2 / #12US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.
NovaScale 5320/6320 Server Specifications Cabinet Dimensions / Weight Unpacked Packed Height: 177.5 cm (70 in) Width: 65.0 cm (25.6 in) Depth: 113 cm (44.5 in) Weight: Main cabinet: 590 kg (1300 lb) I/O cabinet: 300 kg (661 lb) Height: 202 cm (79.5 in) Width: 80.0 cm (31.5 in) Depth: 127.5 cm (50.
Power Cables PDU-0-7-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 ( 3 x 6 mm2 / #10US) IEC60309-32A CSS Module AC (20A) Cable type Connector type 1 per CSS Module 3 x AWG12 (3 x 4mm2 / #12US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.
NovaScale 5085 Server Specifications NovaScale 5085 Servers are delivered rack-mounted in 40U or 19U cabinets. Cabinet Dimensions / Weight Unpacked 1300H Height: Width: Depth: Weight (max): 1300L Height: Width: Depth: Weight (max.): Packed 195.5 cm (77.0 in) 60.0 cm (23.6 in) 129.5 cm (51.0 in) 340 kg (725 lb) 1300H Height: Width: Depth: Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 140.0 cm (55.1 in) 370 kg (790 lb) 103.5 cm (40.7 in) 60.0 cm (23.6 in) 129.5 cm (51.
Power Cables PDU-2-4-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 ( 3 x 6 mm2 / #10US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.5 meters for connection inside the cabinet.
NovaScale 5165 Server Specifications NovaScale 5165 Servers are delivered rack-mounted in 40U or 19U cabinets. Cabinet Dimensions / Weight Unpacked 1300H Height: Width: Depth: Weight (max): 1300L Height: Width: Depth: Weight (max.): Packed 195.5 cm (77.0 in) 60.0 cm (23.6 in) 129.5 cm (51.0 in) 450 kg (959 lb) 1300H Height: Width: Depth: Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 140.0 cm (55.1 in) 480 kg (1022 lb) 103.5 cm (40.7 in) 60.0 cm (23.6 in) 129.5 cm (51.
Acoustic Power at Room Temperature +20° C (+68° F) System Running Lw(A) 6.3 Bels System Idle Lw(A) 6.1 Bels Power Cables PDU-2-4-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 (3 x 6 mm2 / #10US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.
NovaScale 5245 Server Specifications NovaScale 5245 Servers are delivered rack-mounted in 40U cabinets. Cabinet Dimensions / Weight Unpacked 1300H Height: Width: Depth: Weight (max): Packed 195.5 cm (77.0 in) 60.0 cm (23.6 in) 129.5 cm (51.0 in) 560 kg (1193 lb) 1300H Height: Width: Depth: Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 140.0 cm (55.
Power Cables PDU-2-4-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 (3 x 6 mm2 / #10US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.5 meters for connection inside the cabinet.
NovaScale 5325 Server Specifications NovaScale 5325 Servers are delivered rack-mounted in 40U cabinets. Cabinet Dimensions / Weight Unpacked 1300H Height: Width: Depth: Weight (max): Packed 195.5 cm (77.0 in) 60.0 cm (23.6 in) 129.5 cm (51.0 in) 670 kg (1427 lb) 1300H Height: Width: Depth: Weight (max): 200.0 cm (78.7 in) 80.0 cm (31.5 in) 140.0 cm (55.
Power Cables PDU-2-4-M-32A AC (32A) Cable type Connector type 1 per PDU 3 x AWG10 (3 x 6 mm2 / #10US) IEC60309-32A It is mandatory for power lines and terminal boxes to be located within the immediate vicinity of the system and to be easily accessible. Each power line must be connected to a separate, independent electrical panel and bipolar circuit breaker. PDUs require an extra cable length of 1.5 meters for connection inside the cabinet.
Smart UPS References UPS Type 3KVA 5KVA 7.5KVA 10KVA 8.9cm (3.5in) 48.3cm (19in) 66cm (26in) 43.6kg (96.0lb) 13cm (3.
Appendix B. Conversion Tables Imperial to Metric 1 inch (") 2.54 cm (centimeters) 1 foot (') (12 inches) 30.48 cm 1 yards (yd) (3 feet) 0.91 m (meters) 1 mile (mi) (1760 yards) 1.6093 km (kilometers) 1 pound (avdp) (lb) 0.5 kg (kilograms) 1 ounce (avdp) (oz) 28.4 g (grams) 1 square foot (ft2) 0.093 m2 (square meters) 1 square inch (in2) 6.5 cm2 (square centimeters) 1 square yard (yd2) 0.8 m2 (square meters) 1 acre 0.4 ha (hectares) 1 cubic foot (ft3) 0.
Celsius to Fahrenheit Conversion Multiply the temperature in Celsius by 9, divide by 5 and add 32: (C x 9/5) + 32 = F Fahrenheit to Celsius Conversion Subtract 32 degrees from the temperature in Fahrenheit, multiply by 5 and divide by 9: (F - 32) x 5/9 = C B-2 Site Preparation Guide
Index A H Air Heat dissipation, 3-1 Hygrometry, control, 3-1 circulation, 3-3 distribution, 3-2 filtering, 3-2 pollution, 3-2 renewal, 3-2 Air conditioning, 3-1 features, 3-1 functions, 3-1 specifications, 3-2 Alarms, temperature, 3-5 C Cable, cut-outs, 2-3 Cables, network, 2-4 Cabling, 2-3 requirements, 4-2 Carry-in, route, 1-2 Ceiling, 2-10 suspended, 2-10 Cleaning, 2-11 Connection, neutral point, 4-6 Control hygrometry, 3-1 temperature, 3-1 D Delivery, 1-2 Dynamic safety, 3-5 E Electromagnetic com
Site, layout grid, 2-6 Sound-proofing, 2-11 Specifications air-conditioning, 3-2 Blade 2020, A-5 Blade 2021, A-5 Blade 2040, A-5 Blade 2320, A-6 chassis, NovaScale Blade, A-4 atmospheric, xiii electrical, xiii NovaScale 20xx Cabinets, A-2 NovaScale 3xx5 Cabinets, A-7 NovaScale 4020 Server, A-14 NovaScale 4040 Server, A-15 NovaScale 5080/5160 Servers, A-16 NovaScale 5085 Servers, A-20 NovaScale 5165 Server, A-22 NovaScale 5245 Server, A-24 NovaScale 5320/6320 Servers, A-18 NovaScale 5325 Server, A-26 X-2 S
Technical publication remarks form Title : NOVASCALE NovaScale Servers Site Preparation Guide Reference: 86 A1 87EF 08 Date: December 2006 ERRORS IN PUBLICATION SUGGESTIONS FOR IMPROVEMENT TO PUBLICATION Your comments will be promptly investigated by qualified technical personnel and action will be taken as required. If you require a written reply, please include your complete mailing address below.